Predictika · PV inverter array and connection design validator, modeled on the SMA Sunny Tripower X
A quoting agent for a solar installer prepares a quote for a commercial rooftop array on a Sunny Tripower X inverter: the modules per string, the strings on each input, the grid connection, the protection and the cables. Before the quote is released, the agent sends it to Predictika's validator, which checks the design against the inverter's published limits and reports every problem it finds in one pass.
This validator checks any array design for the modeled inverters, not just the scenarios shown below.
Any array design for these inverters that touches these rules is in scope, not only the scenarios pictured here. Not checked: prices, energy yield, shading, mounting and the accuracy of the module data the caller states.
7 scenarios in 3 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: quoting agent for Bayline Solar (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical catalog compatibility check (a module and an inverter that are listed as a pair, each limit checked on its own) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | A catalog compatibility check | Predictika |
|---|---|---|
| Limits that depend on the string length | Only with workarounds The cold string voltage is the number of modules times the module voltage on the coldest day, and the MPP voltage and the hottest-day voltage need the same multiplication with other module figures. | The voltages are computed from the modules per string inside the model, and every limit is checked in the same pass. |
| Currents that depend on how the strings are spread | Only with care The current on an input depends on how many strings sit on it, so the same total number of strings can pass or fail. | The strings on each input are in one request and the busiest input is checked on every call. |
| Stated figures reconciled with the computed ones | Only with workarounds The array power and cold voltage on the quote have to be compared with figures that come from the strings and modules. | The figures are computed inside the model and compared with the stated ones on every call. |
| Installation rules that sit apart from the array | Only with care The grid type, the phases, the residual-current device and the cable sizes are separate conditions that a pairing check does not look at. | Each is a finding of its own and all are returned together. |
| Every problem returned in one answer | Only with workarounds Form checks usually stop at the first failing field, so an agent fixes one error and meets the next. | All findings come back together, whatever order the choices arrived in. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | Each MPP input takes two strings at most, and the current on the busiest input must stay within the maximum usable and short-circuit currents. |
| 2 | The cold string voltage must not exceed 1,000 V, the string voltage on the hottest day must stay above the minimum, and a string outside the MPP voltage range for rated power needs a person to accept the lower output. |
| 3 | The PV array must not exceed the maximum power of the model, and the array power and cold string voltage stated on the quote must match what the modules add up to. |
| 4 | The grid must be TN-C, TN-S, TN-C-S or TT, and the connection must be three-phase. |
| 5 | A residual-current device, if required, must be type A or B rated 100 mA or more, one per inverter. |
| 6 | The AC line and neutral, the grounding conductor and the DC cable must be within their allowed cross-sections. |
| 7 | The PV modules must be protection class II with outputs not grounded, and their coupling capacity to ground must not exceed 6 microfarads. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Quote for Brightwater Dairy: one Sunny Tripower X 25-50 with five strings of 20 modules, 450 W each, three strings on input A and one each on inputs B and C. The modules have 51 V open-circuit voltage on the coldest day. The array is 30,000 Wp and the cold string voltage is 1,020 V. The connection has a type AC residual-current device of 30 mA and an 8 mm2 DC cable. Please validate the quote so I can release it.
Verdict: Blocked.
The agent's request. Revised quote for Brightwater Dairy: one Sunny Tripower X 25-50 with five strings of 10 modules, 450 W each, two strings on inputs A and B and one on input C. The modules have 51 V open-circuit voltage on the coldest day. The array is 22,500 Wp and the cold string voltage is 510 V. The connection has a type B residual-current device of 100 mA and a 4 mm2 DC cable. Please validate the quote so I can release it.
Verdict: Needs approval.
The agent's request. Revised quote for Brightwater Dairy: the same inverter and layout with 11 modules per string. The array is 24,750 Wp and the cold string voltage is 561 V. Please validate the quote so I can release it.
Verdict: Allowed.
The agent's request. Quote for Cedar Ridge Winery: one Sunny Tripower X 15-50 with three strings of 16 modules, 450 W each, one string on each input. The array is 21,600 Wp and the cold string voltage is 816 V. The site has an IT grid with a single-phase connection, 4 mm2 AC line and neutral conductors, a 6 mm2 grounding conductor with no additional grounding, protection class I modules and a module coupling capacity of 8 microfarads. Please validate the quote so I can release it.
Verdict: Blocked.
The agent's request. Revised quote for Cedar Ridge Winery: the same inverter and array on a TN-S three-phase grid, with 10 mm2 AC line and neutral conductors, a 10 mm2 grounding conductor with additional grounding connected, protection class II modules and a module coupling capacity of 1 microfarad. Please validate the quote so I can release it.
Verdict: Allowed.
The agent's request. Quote for Alder Creek Cold Storage: one Sunny Tripower X 20-50 with three strings of 20 modules, 450 W each, 51 V open-circuit voltage per module. The array is 27,000 Wp and the cold string voltage is 1,000 V. Please validate the quote so I can release it.
Verdict: Blocked.
The agent's request. Revised quote for Alder Creek Cold Storage: one Sunny Tripower X 20-50 with three strings of 19 modules, 450 W each, 51 V open-circuit voltage per module. The array is 25,650 Wp and the cold string voltage is 969 V. Please validate the quote so I can release it.
Verdict: Allowed.
The text of the narrated walkthrough, step by step.