Predictika · Split heat pump orders
An AI sales agent prepares an order for an air-to-water split heat pump: model, outdoor unit and hydraulic module, refrigerant line, R32 charge, room volume, heating circuits, options and the charge, capacity and weight figures it states on the quote. Before it goes out, the agent sends it to Predictika, which checks it against a declarative model of the installation notice rules and returns a verdict, every reason and the figures it computed.
This validator models Alfea Extensa A.I. R32 split orders as described in the public installation notice and data sheet, not just the scenarios shown below.
Any Alfea Extensa A.I. R32 order that touches these rules is in scope — not only the scenarios pictured here. Not covered: prices (no public professional price list was found, so this validator produces no price build-up or line-item quote), Combi-Duo and tank variants, the room opening cross-section tables, the ignition-source rule and installation-site conditions beyond the values listed.
7 scenarios in 3 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| A refrigerant charge that grows with the line length | Only with care The added charge, the minimum room volume and the specialist requirement all derive from one length; each model has its own free length and rate. | The length is one input; the charge, the room minimum and the approval are computed together on every call. |
| A second circuit that needs its own kit | Only with workarounds The requirement depends on a choice on one line and a different choice on another, so it needs cross-line rules that interact with the rest. | Every choice is in one request, so the conflict is found whichever order the choices arrive in. |
| Stated charge, capacity and weight that must match the notice | Only with care The values depend on the model, line length and emitter type; each combination needs its own calculation and comparison. | Charge, capacity and weight are computed on every call and compared with the figures the quote states. |
| A room size that depends on the total charge | Only with care The minimum volume is a derived total that depends on the length and the model, and it changes when the room is ventilated. | The total charge and the minimum room volume are computed from the order and checked against the room on every call. |
| Every problem returned in one answer | Only with workarounds Rules tend to fire as the order is saved or a step is completed, so a rep often fixes one error and meets the next. | All findings come back together, whatever order the choices arrived in. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | The heat pump is powered from a single-phase 230 V, 50 Hz supply; a three-phase supply is not listed. |
| 2 | The outdoor unit in the order is not the one paired with this model in the package pairing table (5 and 6 use WOYA060KLT, 8 uses WOYA080KLT, 10 uses WOYA100KLT). |
| 3 | The hydraulic module in the order is not the one paired with this model (5 uses 24,301, 6 and 8 use 24,302, 10 uses 24,303). |
| 4 | The refrigerant line is 2 m; the minimum between the outdoor unit and the hydraulic module is 3 m. |
| 5 | The line is longer than the length covered by the factory charge, so 125 g of R32 must be added; the notice requires an approved specialist for this, so a person should confirm it is arranged. |
| 6 | The line is longer than the length covered by the factory charge, so 375 g of R32 must be added; the notice requires an approved specialist for this, so a person should confirm it is arranged. |
| 7 | The refrigerant line is 31 m; the maximum, with added charge, is 30 m. |
| 8 | The line is longer than the length covered by the factory charge, so 400 g of R32 must be added; the notice requires an approved specialist for this, so a person should confirm it is arranged. |
| 9 | The line is longer than the length covered by the factory charge, so 100 g of R32 must be added; the notice requires an approved specialist for this, so a person should confirm it is arranged. |
| 10 | The height difference between the units is 21 m; the maximum is 20 m. |
| 11 | The gas and liquid line diameters in the order do not match the outdoor unit connections (1/2 inch and 1/4 inch on models 5, 6 and 8; 5/8 inch and 3/8 inch on model 10). |
| 12 | The quote states a total R32 charge of 970 g; the notice rules give 1,095 g (factory charge plus added charge for the line length). |
| 13 | The room is 3 m3; with the total charge of 970 g the minimum room volume is 4 m3 unless the room is ventilated. |
| 14 | The room is 5 m3; with the total charge of 1,630 g the minimum room volume is 6 m3 unless the room is ventilated. |
| 15 | The room is 4 m3; with the total charge of 1,345 g the minimum room volume is 5 m3 unless the room is ventilated. |
| 16 | The room and the adjacent room total 3 m3; with the total charge of 970 g the two rooms together must reach the minimum volume of 4 m3. |
| 17 | The refrigerant line insulation is 10 mm; the notice requires at least 15 mm for the humidity stated. |
| 18 | The refrigerant line insulation is 15 mm; the notice requires at least 20 mm for the humidity stated. |
| 19 | Glass wool is prohibited as refrigerant line insulation. |
| 20 | The heating circuit holds 22 L; a fan-coil circuit must hold at least 23 L, or a buffer tank is needed on the return. |
| 21 | The heating flow temperature is 46 C; this emitter type is limited to 45 C. |
| 22 | The heating flow temperature is 53 C; this emitter type is limited to 52 C. |
| 23 | The design outdoor temperatures are -21 C minimum and 30 C maximum; the heat pump operates from -20 C to +35 C. |
| 24 | The design outdoor temperatures are -7 C minimum and 36 C maximum; the heat pump operates from -20 C to +35 C. |
| 25 | The order has 3 heating circuits; the heat pump manages one or two. |
| 26 | A second heating circuit needs the two-circuit kit (570,630); it is not in the order. |
| 27 | A 6 kW electric backup needs the 6 kW backup relay kit (75,327); it is not in the order. |
| 28 | With the boiler relief kit the electric backup must not be connected; the order has both. |
| 29 | Summer cooling needs the cooling kit (75,328); it is not in the order. |
| 30 | Cooling is described for heating-cooling floors or ceilings and fan-coil units, not for radiators. |
| 31 | Domestic hot water needs both the sanitary kit (73,991) and a mixed sanitary tank; the order has only one of them. |
| 32 | The condensate tray (74,049) is listed for models 5, 6 and 8, not for model 10. |
| 33 | The quote states a heating capacity of 6,000 W; the notice gives 5,500 W at the +7 C outdoor condition for this emitter type. |
| 34 | The quote states a heating capacity of 7,500 W; the notice gives 7,000 W at the +7 C outdoor condition for this emitter type. |
| 35 | The quote states 45 kg for the outdoor unit and hydraulic module; the catalog weights add up to 84 kg. |
| 36 | The circuit holds 10 L; the notice recommends at least 15 L per circuit for this emitter type, so a person should confirm the volume or add a buffer tank. |
| 37 | The circuit holds 11 L; the notice recommends at least 12 L per circuit for this emitter type, so a person should confirm the volume or add a buffer tank. |
| 38 | A breaker rating or cable section differs from the indicative values in the notice; the installer must check them against the electrical standard before the quote goes out. |
| 39 | The refrigerant line is 32 m; the maximum, with added charge, is 30 m. |
| 40 | The quote states a total R32 charge of 970 g; the notice rules give 1,395 g (factory charge plus added charge for the line length). |
| 41 | The quote states 50 kg for the outdoor unit and hydraulic module; the catalog weights add up to 84 kg. |
| 42 | The line is longer than the length covered by the factory charge, so 425 g of R32 must be added; the notice requires an approved specialist for this, so a person should confirm it is arranged. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Please quote a model 6 Alfea Extensa A.I. R32 split heat pump with the WOYA060KLT outdoor unit and the 24302 hydraulic module on a single-phase 230 V supply, serving 1 heating circuit of floor heating at 35 C flow, a 32 m refrigerant line and a 20 m3 installation room. The quote states a total R32 charge of 970 g, a heating capacity of 5,500 W and 84 kg for the outdoor unit and hydraulic module. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a model 6 Alfea Extensa A.I. R32 split heat pump with the WOYA060KLT outdoor unit and the 24302 hydraulic module on a single-phase 230 V supply, serving 1 heating circuit of floor heating at 35 C flow, a 14 m refrigerant line and a 20 m3 installation room. The quote states a total R32 charge of 970 g, a heating capacity of 5,500 W and 84 kg for the outdoor unit and hydraulic module. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a model 8 Alfea Extensa A.I. R32 split heat pump with the WOYA080KLT outdoor unit and the 24302 hydraulic module on a single-phase 230 V supply, serving 2 heating circuits of floor heating at 35 C flow, with summer cooling, a 10 m refrigerant line and a 20 m3 installation room. The quote states a total R32 charge of 1,020 g, a heating capacity of 7,500 W and 87 kg for the outdoor unit and hydraulic module. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a model 8 Alfea Extensa A.I. R32 split heat pump with the WOYA080KLT outdoor unit and the 24302 hydraulic module on a single-phase 230 V supply, serving 2 heating circuits of floor heating at 35 C flow, with summer cooling and the two-circuit kit, a 10 m refrigerant line and a 20 m3 installation room. The quote states a total R32 charge of 1,020 g, a heating capacity of 7,500 W and 87 kg for the outdoor unit and hydraulic module. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a model 8 Alfea Extensa A.I. R32 split heat pump with the WOYA080KLT outdoor unit and the 24302 hydraulic module on a single-phase 230 V supply, serving 2 heating circuits of floor heating at 35 C flow, with summer cooling, the two-circuit kit and the cooling kit, a 10 m refrigerant line and a 20 m3 installation room. The quote states a total R32 charge of 1,020 g, a heating capacity of 7,500 W and 87 kg for the outdoor unit and hydraulic module. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a model 10 Alfea Extensa A.I. R32 split heat pump with the WOYA100KLT outdoor unit and the 24303 hydraulic module on a single-phase 230 V supply, serving 1 heating circuit of floor heating at 35 C flow, with the condensate tray, a 10 m refrigerant line and a 5 m3 installation room. The quote states a total R32 charge of 1,630 g, a heating capacity of 9,500 W and 100 kg for the outdoor unit and hydraulic module. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a model 10 Alfea Extensa A.I. R32 split heat pump with the WOYA100KLT outdoor unit and the 24303 hydraulic module on a single-phase 230 V supply, serving 1 heating circuit of floor heating at 35 C flow, a 10 m refrigerant line and a 12 m3 installation room. The quote states a total R32 charge of 1,630 g, a heating capacity of 9,500 W and 107 kg for the outdoor unit and hydraulic module. It is ready to send.
Verdict: Allowed.
The text of the narrated walkthrough, step by step.