Predictika · AC-DC power shelf orders
An AI sales agent prepares an order for Bel Power Solutions AC-DC power shelves: the input type, the output and busbar style, the redundancy, how many shelves and network attached controllers, and the room the shelves will run in. Before the order goes out, the agent sends it to Predictika, which checks it against a declarative model of the Bel shelf reference table and the SPSTET4 and SPSPFE3 datasheets and returns a verdict, every reason and the figures it computed.
This validator models orders for Bel Power Solutions AC-DC power shelves, not just the scenarios shown below.
Any order for these shelves is in scope — not only the scenarios pictured here. Not covered: prices (the datasheets list none, so this validator produces no price build-up or line-item quote), the ratings of the shelves other than SPSTET4 and SPSPFE3, parallel operation of SPSPFE3 shelves (the datasheet does not describe it, so it goes to a person) and accessories and cabling. Product details change; the model reflects the datasheets and reference table as read in October 2026.
6 scenarios in 3 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| Nine shelves ordered for a bus that takes eight in parallel | Only with care A quantity limit has to be written for the shelf model and kept in step with the datasheet. | The shelf count is checked against the model limit on every call. |
| An input and output pairing the reference table does not offer, or offers only on request | Only with workarounds The table is a matrix of six inputs by eight outputs with three kinds of cell; it is usually kept in a lookup that has to be copied from the PDF. | The whole table is in the model, so a missing pairing blocks and an on-request pairing goes to a person, in one answer. |
| A load or a stated capacity that is more than the shelves deliver at that room temperature | Only with workarounds The capacity changes with redundancy, temperature and altitude, so the rule needs a formula; the stated figure is a free-entry field that has to be compared with it. | The capacity is computed from the model and compared with both the load and the stated figure on every call. |
| Two controllers for one power zone, or for one shelf | Only with care A rule per controller option, written against a count somewhere else on the order. | Shelves, zones and controllers are checked together. |
| Every problem returned in one answer | Only with workarounds Rules tend to fire as the order is saved or a step is completed, so a rep often fixes one error and meets the next. | All findings come back together, whatever order the choices arrived in. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | Up to 8 SPSTET4 power shelves can be configured for parallel operation; the order has 9. |
| 2 | The SPSTET4 power shelf is a 6+0 configuration; 3+3 and 5+1 are not offered on it. |
| 3 | 2 network attached controllers are ordered for 1 power zone(s); install only 1 controller per power zone. |
| 4 | 2 network attached controllers are ordered for 1 shelf(ves); each shelf has one controller slot. |
| 5 | The load is 100,000 W but the shelves deliver 96,000 W together at this ambient temperature and altitude. |
| 6 | The load is 80,000 W but the shelves deliver 72,000 W together at this ambient temperature and altitude. |
| 7 | 40 C at 2,500 m is outside the operating range: full load to 35 C up to 4,000 m, to 45 C up to 1,800 m, and 75 percent load to 55 C up to 1,800 m. |
| 8 | 20 C at 4,500 m is outside the operating range: full load to 35 C up to 4,000 m, to 45 C up to 1,800 m, and 75 percent load to 55 C up to 1,800 m. |
| 9 | 56 C at 0 m is outside the operating range: full load to 35 C up to 4,000 m, to 45 C up to 1,800 m, and 75 percent load to 55 C up to 1,800 m. |
| 10 | -5 C at 0 m is outside the operating range: full load to 35 C up to 4,000 m, to 45 C up to 1,800 m, and 75 percent load to 55 C up to 1,800 m. |
| 11 | The order states 100,000 W of capacity; the validator computes 96,000 W at this ambient temperature and altitude. |
| 12 | The load is 9,000 W but the shelves deliver 8,700 W together at this ambient temperature and altitude. |
| 13 | The SPSPFE3 power shelf is configured as 3+3 or 5+1; 6+0 is not offered on it. |
| 14 | The load is 13,000 W but the shelves deliver 10,800 W together at this ambient temperature and altitude. |
| 15 | The order states 14,400 W of capacity; the validator computes 10,800 W at this ambient temperature and altitude. |
| 16 | The SPSPFE3 datasheet does not describe running several shelves in parallel; a person should confirm it. |
| 17 | The shelf reference table lists no power shelf with this input type and this output and busbar style. |
| 18 | Bel lists this shelf as available on request, requiring a short design cycle; a person should confirm it with the factory. |
| 19 | The shelf is in the Bel reference table, but its ratings, controller option and parallel use are not in the datasheets this validator covers; a person should confirm them. |
| 20 | The order has 0 shelves; at least one is needed. |
| 21 | 3 network attached controllers are ordered for 2 power zone(s); install only 1 controller per power zone. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Please quote 9 power shelves with the 277/480 V Y input and the 48 V offset long busbar, in a 6+0 configuration, with 2 network attached controllers for 1 power zone, for a load of 190,000 W, running at 30 C. The order states 216,000 W of capacity. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote 8 power shelves with the 277/480 V Y input and the 48 V offset long busbar, in a 6+0 configuration, with 1 network attached controller for 1 power zone, for a load of 190,000 W, running at 30 C. The order states 192,000 W of capacity. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote 1 power shelf with the 208 V delta input and the 12 V single straight busbar, in a 5+1 configuration, with 0 network attached controllers for 1 power zone, for a load of 13,000 W, running at 50 C. The order states 14,400 W of capacity. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote 1 power shelf with the 208 V delta input and the 12 V single straight busbar, in a 5+1 configuration, with 0 network attached controllers for 1 power zone, for a load of 13,000 W, running at 40 C. The order states 14,400 W of capacity. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote 2 power shelves with the 240/415 V Y input and the 48 V offset short busbar, in a 6+0 configuration, with 0 network attached controllers for 1 power zone, running at 25 C. It is ready to send.
Verdict: Needs approval.
The agent's request. Please quote 2 power shelves with the 3x230 V input and the 48 V offset long busbar, in a 6+0 configuration, with 0 network attached controllers for 1 power zone, running at 25 C. It is ready to send.
Verdict: Blocked.
The text of the narrated walkthrough, step by step.