Predictika · Pressure transmitter orders for instrumentation buyers
An AI sales agent prepares an order for a Dwyer Series 616W differential pressure transmitter with its range, display, output, power supply, wiring and tubing. Before it goes out, the agent sends it to Predictika, which checks it against a declarative model of the public Dwyer bulletin and returns a verdict and every reason.
This validator models Series 616W orders placed from the model chart and the specifications in Dwyer Bulletin P-616W-1, not just the scenarios shown below.
Any order that touches these rules is in scope — not only the scenarios pictured here. Not covered: prices (the bulletin has none, so this validator produces no price build-up or line-item quote), wetted-material compatibility with a specific gas (the bulletin says to consult the factory), accessories, and installation practice beyond the stated limits.
7 scenarios in 3 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| A range that must match the need | Only with care The model range is fixed at the factory, so a mismatch between the range ordered and the range needed has to be a product rule tied to a customer requirement kept on another line. | The range ordered and the range needed are in one request and are compared directly. |
| Limits that depend on the output chosen | Only with care The allowed supply window, the loop resistance limit and the load rule all change with the output and power type, so the rules reach across lines. | Every choice is in one request, so the conflict is found whatever order the choices arrive in. |
| A loop limit computed from the supply voltage | Only with workarounds The maximum loop resistance grows with the supply voltage, so a fixed number does not work; it usually becomes a lookup table or is left to the engineer. | The limit is computed from the supply voltage and shown with the finding. |
| A recommendation that a person confirms | Only with workarounds A hose clamp that is recommended but not required is not a hard stop; it usually becomes a blocking rule or is left out. | It is returned as an approval item, separate from the blocking findings. |
| Every problem returned in one answer | Only with workarounds Rules tend to fire as the order is saved or a step is completed, so a buyer often fixes one error and meets the next. | All findings come back together, whatever order the choices arrived in. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | The bidirectional (B) and kPa (M) ranges are listed only as LCD models; the order has no LCD. |
| 2 | The transmitter is factory calibrated to its model range and the span and zero controls are for checking calibration, not re-ranging; the model range is not the range the customer needs. |
| 3 | The customer wants a digital display, and the model on the order has none. |
| 4 | The Series 616W is for air and non-combustible, compatible gases only. |
| 5 | The line pressure (80 in units of 0.1 psig) is above the maximum pressure of this model (60 in units of 0.1 psig). |
| 6 | The ambient temperature 75 C is outside the limits of -20 to 70 C. |
| 7 | The ambient temperature -25 C is outside the limits of -20 to 70 C. |
| 8 | The terminal block takes 16 to 26 AWG wire; the order has 28 AWG. |
| 9 | The terminal block takes 16 to 26 AWG wire; the order has 14 AWG. |
| 10 | The barbed process connections fit 1/8 inch and 3/16 inch I.D. tubing only. |
| 11 | The 4-20 mA current output is a 2-wire DC loop powered at 10-36 VDC; AC power is for the 3-wire voltage output. |
| 12 | Simultaneous current and voltage outputs are not designed for AC voltage operation; a DC power supply must be used. |
| 13 | A voltage output needs a 0-5 V or 0-10 V range choice (DIP switch 4); the order has none. |
| 14 | The 0-5 V or 0-10 V range applies only to the voltage output; the order has a current output only. |
| 15 | The supply voltage 99 (in tenths of a volt) is outside the 100 to 360 allowed for this output and power type. |
| 16 | The supply voltage 160 (in tenths of a volt) is outside the 170 to 360 allowed for this output and power type. |
| 17 | The supply voltage 361 (in tenths of a volt) is outside the 100 to 360 allowed for this output and power type. |
| 18 | The supply voltage 210 (in tenths of a volt) is outside the 216 to 330 allowed for this output and power type. |
| 19 | The current loop resistance of 800 ohms is above the 700 ohms this supply voltage allows. |
| 20 | The current loop resistance of 1260 ohms is above the 1250 ohms this supply voltage allows. |
| 21 | The current loop resistance of 400 ohms is above the 350 ohms this supply voltage allows. |
| 22 | The voltage output needs a receiver load of at least 1000 ohms; the order has 800 ohms. |
| 23 | The bulletin recommends a suitable hose clamp on ranges over 20 psi, and the order has none; the customer should confirm. |
| 24 | The ambient temperature 90 C is outside the limits of -20 to 70 C. |
| 25 | The terminal block takes 16 to 26 AWG wire; the order has 30 AWG. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Please order a Series 616W transmitter in the 0 to 20 in w.c. range with no display, for a customer who needs the 0 to 10 in w.c. range and wants a digital display, with a 0-10 V voltage output, powered from 12.0 V DC, a line pressure of 2.0 psig, 18 AWG wire and 3/16 inch tubing. It is ready to send.
Verdict: Blocked.
The agent's request. Please order a Series 616W transmitter in the 0 to 10 in w.c. range with an LCD, for a customer who needs the 0 to 10 in w.c. range and wants a digital display, with a 0-10 V voltage output, powered from 24.0 V DC, a line pressure of 2.0 psig, 18 AWG wire and 3/16 inch tubing. It is ready to send.
Verdict: Allowed.
The agent's request. Please order a Series 616W transmitter in the 0 to 100 in w.c. range with an LCD, for a customer who needs the 0 to 100 in w.c. range and wants a digital display, with a 4-20 mA current output, powered from 24.0 V DC, with a current loop resistance of 900 ohms, a line pressure of 10.0 psig, 18 AWG wire and 1/4 inch tubing. It is ready to send.
Verdict: Blocked.
The agent's request. Please order a Series 616W transmitter in the 0 to 100 in w.c. range with an LCD, for a customer who needs the 0 to 100 in w.c. range and wants a digital display, with a 4-20 mA current output, powered from 30.0 V DC, with a current loop resistance of 900 ohms, a line pressure of 10.0 psig, 18 AWG wire and 3/16 inch tubing. It is ready to send.
Verdict: Allowed.
The agent's request. Please order a Series 616W transmitter in the 0 to 40 in w.c. range with an LCD, for a customer who needs the 0 to 40 in w.c. range and wants a digital display, with both a 4-20 mA current output and a 0-5 V voltage output, powered from 24.0 V AC, with a current loop resistance of 250 ohms, a line pressure of 22.0 psig, 14 AWG wire and 3/16 inch tubing. It is ready to send.
Verdict: Blocked.
The agent's request. Please order a Series 616W transmitter in the 0 to 40 in w.c. range with an LCD, for a customer who needs the 0 to 40 in w.c. range and wants a digital display, with both a 4-20 mA current output and a 0-5 V voltage output, powered from 24.0 V DC, with a current loop resistance of 250 ohms, a line pressure of 22.0 psig, 18 AWG wire and 3/16 inch tubing. It is ready to send.
Verdict: Needs approval.
The agent's request. Please order a Series 616W transmitter in the 0 to 40 in w.c. range with an LCD, for a customer who needs the 0 to 40 in w.c. range and wants a digital display, with both a 4-20 mA current output and a 0-5 V voltage output, powered from 24.0 V DC, with a current loop resistance of 250 ohms, a line pressure of 22.0 psig with a hose clamp, 18 AWG wire and 3/16 inch tubing. It is ready to send.
Verdict: Allowed.
The text of the narrated walkthrough, step by step.