Predictika · Eaton low-voltage switchboard quotes
An AI sales agent prepares a quote for an Eaton xEnergy Main low-voltage switchboard: incomer, main busbar, outgoing feeder breakers, form of separation, enclosure rating, sections and discount, in euros. Before it goes out, the agent sends it to Predictika, which checks it against a declarative model of the configuration and quoting rules, compares the total and section count the quote states with the computed ones, and returns every finding together with the line-item quote. This is an illustrative model built from Eaton's public product information with fictional prices; it is not Eaton's internal rule set.
This validator models one product line: Eaton's xEnergy Main low-voltage switchboards built to IEC 61439-2, with IZMX air circuit breaker incomers and NZM molded-case circuit breaker feeders. It handles any quote involving these components, not only the scenarios shown on this page. It does not cover Eaton's medium-voltage switchgear, busway, UPS or power-distribution-unit lines.
7 scenarios in 4 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| Busbar derating by enclosure rating against the incomer | Only with workarounds The busbar current falls as the enclosure rating rises, so a 2500 A busbar in an IP54 enclosure carries less than the 2500 A incomer feeding it. That is a calculated comparison across two lines, which rules-based CPQ handles with custom code or leaves to a reviewer. | The derated busbar rating is computed from the enclosure rating and compared with the incomer on every call; the finding gives both figures. |
| Fault level checked against three components at once | Only with care The incomer, the busbar and every feeder breaker each have their own short-circuit rating. A rule per component works, but each combination of ratings needs its own rule and one missing rule lets a weak breaker through. | All three ratings are compared with the prospective fault current on every call, so one board can come back with three separate findings. |
| Section count and line-up length from feeders per section | Only with workarounds How many sections a board needs depends on how many of each feeder frame fit in a section of the chosen width. Turning that into a section count, a length and a room limit is arithmetic across lines, not an option exclusion. | Sections, length and the room and busbar-system limits are computed together and priced into the quote. |
| Discount authority that depends on the size of the board | Only with care The approval limit rises with the hardware list price, so the same discount can need approval on a large board and be refused on a small one. Several bands in a price rule are easy to leave out of step. | The sales engineer limit and the maximum for the board size are checked on every call: 35 percent is blocked and 18 percent goes to approval on the same board. |
| Stated total and section count that must match the computed ones | Only with workarounds A validation rule can compare a stated figure with a calculated one only if the stated figure is a field on the quote, which it rarely is. | The stated total and the stated section count travel with the quote and are compared with the computed values on every call. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | 13 sections exceed the 12 sections one main busbar system supports; split the board. |
| 2 | 18 percent discount is above the 10 percent a sales engineer can give; approvable up to 20 percent. |
| 3 | 21 percent discount exceeds the 20 percent that can be approved on €33,850.00. |
| 4 | A feeder frame is wider than the 800 mm sections selected; use wider sections. |
| 5 | An outgoing feeder breaker has breaking capacity below 70 kA; use a high-break frame. |
| 6 | Busbar short-time rating 65 kA is below the 70 kA prospective fault current. |
| 7 | Feeders total 4000 A at 60 percent diversity exceed the 1600 A incomer; design engineering must confirm the diversity. |
| 8 | Form 4b requires plug-in or withdrawable feeders; fixed breakers were selected. |
| 9 | Incomer breaking capacity 50 kA is below the 60 kA prospective fault current. |
| 10 | Internal arc containment is offered only with Form 4a or 4b separation. |
| 11 | Lead time is about 8 weeks; the customer needs delivery in 6. |
| 12 | Line-up length 13000 mm exceeds the 12000 mm available. |
| 13 | Main busbar derated to 2125 A at IP54 is below the 2500 A incomer. |
| 14 | Maximum demand 1800 A exceeds the 1600 A incomer. |
| 15 | Stated section count does not match: the agent stated 4 sections; the validator computes 5. |
| 16 | Stated total does not match: the agent stated €51,701.38; the validator computes €54,422.50. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Quote for Brightwave Power: a 2500 A IZMX40 incomer with a 2500 A main busbar, Form 4b, IP54, for a 70 kA prospective fault level and 2,200 A maximum demand. Feeders are 8 NZM3 630 A withdrawable and 12 NZM2 250 A plug-in breakers in 800 mm sections at 30 percent diversity. Needed in 16 weeks, with an 8 percent discount. The quote states a total of €111,090.00 across 5 sections. It is ready to send.
Verdict: Blocked.
The agent's request. Quote for Brightwave Power: a 2500 A IZMX40 incomer with a 3200 A main busbar, Form 4b, IP54, for a 70 kA prospective fault level and 2,200 A maximum demand. Feeders are 8 NZMH3 630 A high-break withdrawable and 4 NZM4 1600 A withdrawable breakers in 1000 mm sections at 20 percent diversity. Needed in 16 weeks, with an 8 percent discount. The quote states a total of €137,678.00 across 5 sections. It is ready to send.
Verdict: Allowed.
The agent's request. Quote for Halden Data: a 4000 A IZMX40 incomer with a 4000 A main busbar, Form 4b, for a 65 kA prospective fault level and 3,600 A maximum demand. Feeders are 24 NZM4 1600 A withdrawable breakers in 1000 mm sections at 10 percent diversity, in a switchgear room 12,000 mm long. Needed in 16 weeks, with an 8 percent discount. The quote states a total of €361,146.00 across 13 sections. It is ready to send.
Verdict: Blocked.
The agent's request. Quote for Halden Data: a 4000 A IZMX40 incomer with a 4000 A main busbar, Form 4b, for a 65 kA prospective fault level and 3,600 A maximum demand. Feeders are 22 NZM4 1600 A withdrawable breakers in 1000 mm sections at 10 percent diversity, in a switchgear room 12,000 mm long. Needed in 16 weeks, with an 8 percent discount. The quote states a total of €334,420.00 across 12 sections. It is ready to send.
Verdict: Allowed.
The agent's request. Quote for Ridgeline Utilities: a 2500 A IZMX40 incomer with a 2500 A main busbar, Form 4b, for a 50 kA prospective fault level and 2,200 A maximum demand. Feeders are 6 NZM3 630 A withdrawable and 12 NZM2 250 A plug-in breakers at 35 percent diversity. Needed in 14 weeks, with a 35 percent discount. The quote states a total of €71,077.50 across 5 sections. It is ready to send.
Verdict: Blocked.
The agent's request. Quote for Ridgeline Utilities: a 2500 A IZMX40 incomer with a 2500 A main busbar, Form 4b, for a 50 kA prospective fault level and 2,200 A maximum demand. Feeders are 6 NZM3 630 A withdrawable and 12 NZM2 250 A plug-in breakers at 35 percent diversity. Needed in 14 weeks, with an 18 percent discount. The quote states a total of €89,667.00 across 5 sections. It is ready to send.
Verdict: Needs approval.
The agent's request. Quote for Stonebridge Works: a 1600 A IZMX16 incomer with a 1600 A main busbar, Form 2b, for a 50 kA prospective fault level and 1,400 A maximum demand. Feeders are 16 NZM2 250 A fixed breakers in 600 mm sections at 40 percent diversity, with a factory acceptance test. Needed in 10 weeks, with a 5 percent discount. The quote states a total of €51,701.38 across 3 sections. It is ready to send.
Verdict: Blocked.
The text of the narrated walkthrough, step by step.