Predictika · Reserve power batteries
An AI sales agent prepares a quote for a bank of EnerSys PowerSafe SBS EON batteries: the model, how many are wired in series and in parallel, the charger and its setting, the temperature and how the batteries are stored and installed. Before it goes out, the agent sends it to Predictika, which checks it against a declarative model of EnerSys's published data and operating rules and returns a verdict, every reason and the figures it computed.
This validator models quotes for PowerSafe SBS EON banks built on EnerSys's range summary and its installation, operation and maintenance manual, not just the scenarios shown below.
Any PowerSafe SBS EON bank quote that touches these rules is in scope — not only the scenarios pictured here. Not covered: prices (EnerSys publishes none for these batteries), limits on parallel strings (the manual gives none), other EnerSys battery ranges, fast-charge and partial-state-of-charge duty, cabinets, racks and connectors, and sizing a bank from a load profile. Assumptions: the capacity is the 10 hour rate to 1.80 V per cell at 20 degrees C; the cyclic charge voltage is checked at 20 degrees C only; a discharge time on a boundary of the manual's table takes the lower of the two voltages; and the source documents are EnerSys's French range summary and Spanish manual.
7 scenarios in 3 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| A charge setting that depends on the temperature | Only with care A lookup or formula by temperature with a floor. It works, but the correction and the 2,210 mV minimum have to be kept in step with the manual. | The recommended setting is worked out from the temperature on every call and compared with the setting the agent states. |
| A charger that must cover the capacity, the strings and the load | Only with care A calculation from the model, the number of strings and the load, compared with the charger rating. Each model has its own capacity to look up. | The capacity of the chosen model and the strings is looked up and the needed current is compared with the charger. |
| Stated voltage, capacity and weight that must match the bank | Only with care Stated figures are free-entry fields; a rule can compare them with computed ones, but the weight and capacity tables for 24 models are easy to get wrong. | The stated figures travel with the quote and are compared with the computed ones on every call. |
| Limits that depend on the application and the cell type together | Only with workarounds Horizontal installation is advised only for 2 V cells on cyclic duty, so one rule has to read the application, the model and the orientation. | The application, the model type and the orientation are in one request and are checked with the rest. |
| Every problem returned in one answer | Only with workarounds Rules tend to fire as the quote is saved or a step is completed, so a rep often fixes one error and meets the next. | All findings come back together, whatever order the choices arrived in. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | The order needs at least one block or cell in series and at least one string. |
| 2 | The operating temperature of -41 degrees C is outside the -40 to +50 degrees C range of the batteries. |
| 3 | The operating temperature of 51 degrees C is outside the -40 to +50 degrees C range of the batteries. |
| 4 | The charger is set to 2,290 mV per cell; the manual recommends 2,210 mV per cell for this application at 45 degrees C. |
| 5 | The charger is set to 2,209 mV per cell; the minimum charge voltage at any temperature is 2,210 mV per cell. |
| 6 | The manual gives the cyclic charge voltage of 2,400 mV per cell at 20 degrees C only; at 25 degrees C a person should confirm the temperature compensation. |
| 7 | For cyclic duty the manual advises a low-voltage disconnect at 1,930 mV per cell (80 percent depth of discharge); the setting is 0 mV per cell (0 means none). |
| 8 | For cyclic or hybrid duty EnerSys recommends installing the 2 V SBS 320 to SBS 3900 cells horizontally; a person should confirm an upright installation. |
| 9 | The batteries cannot be installed upside down; any other orientation is allowed. |
| 10 | The charger can deliver 38 A; the manual calls for at least 39 A, which is 0.1 times the 10 hour capacity of the bank plus the load on float duty. |
| 11 | An end-of-discharge voltage of 1,649 mV per cell is below the 1,650 mV per cell the manual recommends for a discharge of 5 minutes. |
| 12 | The manual lists end-of-discharge voltages only for discharges of 5 minutes to 20 hours; 4 minutes is outside that range. |
| 13 | 25 months in storage at 20 degrees C is longer than the 24.0 months the manual allows before a refresh charge; the batteries need a refresh charge before use. |
| 14 | The manual gives storage times only for 10, 15, 20, 25, 30, 35 and 40 degrees C; 22 degrees C is not listed. |
| 15 | The quote states a nominal bank voltage of 24 V; the blocks in series give 48 V. |
| 16 | The quote states a bank capacity of 92 Ah; the strings give 184 Ah at the 10 hour rate. |
| 17 | The quote states a total weight of 200.0 kg; the blocks weigh 224.0 kg in total. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Please quote Northgate Telecom Services a PowerSafe SBS EON battery bank of 4 SBS C11 blocks in series in each of 3 parallel strings, on float (standby) duty, installed upright, at 20 degrees C, charged at 2,330 mV per cell from a 55 A charger with a 30 A load, designed for a 480 minute discharge to 1,800 mV per cell. The quote states a nominal bank voltage of 48 V, a bank capacity of 368 Ah and a total weight of 336.0 kg. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote Northgate Telecom Services a PowerSafe SBS EON battery bank of 4 SBS C11 blocks in series in each of 3 parallel strings, on float (standby) duty, installed upright, at 20 degrees C, charged at 2,290 mV per cell from a 60 A charger with a 30 A load, designed for a 480 minute discharge to 1,800 mV per cell. The quote states a nominal bank voltage of 48 V, a bank capacity of 276 Ah and a total weight of 336.0 kg. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote Northgate Telecom Services a PowerSafe SBS EON battery bank of 4 SBS 100 blocks in series in each of 2 parallel strings, on float (standby) duty, installed upright, at 45 degrees C, charged at 2,290 mV per cell from a 45 A charger with a 25 A load, designed for a 480 minute discharge to 1,800 mV per cell, and stored for 14 months at 30 degrees C before installation. The quote states a nominal bank voltage of 48 V, a bank capacity of 200 Ah and a total weight of 260.8 kg. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote Northgate Telecom Services a PowerSafe SBS EON battery bank of 4 SBS 100 blocks in series in each of 2 parallel strings, on float (standby) duty, installed upright, at 45 degrees C, charged at 2,210 mV per cell from a 45 A charger with a 25 A load, designed for a 480 minute discharge to 1,800 mV per cell, and stored for 14 months at 30 degrees C before installation. The quote states a nominal bank voltage of 48 V, a bank capacity of 200 Ah and a total weight of 260.8 kg. It is ready to send.
Verdict: Needs approval.
The agent's request. Please quote Northgate Telecom Services a PowerSafe SBS EON battery bank of 24 SBS 400 cells in series in each of 3 parallel strings, on cyclic duty, installed upside down, at 20 degrees C, charged at 2,290 mV per cell from a 140 A charger, designed for a 480 minute discharge to 1,800 mV per cell, with no low-voltage disconnect. The quote states a nominal bank voltage of 48 V, a bank capacity of 1,200 Ah and a total weight of 1,728.0 kg. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote Northgate Telecom Services a PowerSafe SBS EON battery bank of 24 SBS 400 cells in series in each of 3 parallel strings, on cyclic duty, installed upright, at 20 degrees C, charged at 2,400 mV per cell from a 140 A charger, designed for a 480 minute discharge to 1,800 mV per cell, with no low-voltage disconnect. The quote states a nominal bank voltage of 48 V, a bank capacity of 1,200 Ah and a total weight of 1,728.0 kg. It is ready to send.
Verdict: Needs approval.
The agent's request. Please quote Northgate Telecom Services a PowerSafe SBS EON battery bank of 24 SBS 400 cells in series in each of 3 parallel strings, on cyclic duty, installed horizontally, at 20 degrees C, charged at 2,400 mV per cell from a 140 A charger, designed for a 480 minute discharge to 1,800 mV per cell, with a low-voltage disconnect at 1,930 mV per cell. The quote states a nominal bank voltage of 48 V, a bank capacity of 1,200 Ah and a total weight of 1,728.0 kg. It is ready to send.
Verdict: Allowed.
The text of the narrated walkthrough, step by step.