An AI sales agent sizes a battery storage project for a developer: a number of B-VAULT units, AC-coupled or DC-coupled, with a 2-hour or 4-hour discharge, against the power and energy the project needs, the temperature and altitude of the site, the DC voltage of the customer's inverter and the total power it states. Before it goes out, the agent sends it to Predictika, which checks it against a declarative model of the figures in the public Energy Vault B-VAULT datasheet and returns a verdict, every reason and the figures it computed.
This validator models the sizing of a B-VAULT project from the public Energy Vault B-VAULT datasheet, not just the scenarios shown below.
Any project built from B-VAULT units at 2-hour or 4-hour duration is in scope — not only the scenarios pictured here. Not covered: prices (Energy Vault publishes no list prices, so this page shows no price build-up), long-term service agreements, other Energy Vault products, grid frequency (the datasheet row could not be read unambiguously), interconnection and permitting, and real project performance.
7 scenarios in 3 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| Power and energy that scale with the number of units and the duration | Only with care The power per unit changes with the discharge duration, and energy and power are two separate comparisons against the project's needs. | Both are computed from the units and the duration on every call. |
| Limits that differ between AC- and DC-coupled units | Only with workarounds The temperature range, the inverter and the voltage window depend on the coupling, so a rules-based CPQ needs separate rule sets per configuration. | The coupling selects the limits inside one model, in any order of choices. |
| Inverter compatibility that is not published | Only with care A rule can flag an unlisted inverter, but someone has to remember to route it to a person. | It is a named approval finding, with the reason, that comes back with the verdict. |
| Total power the project states | Only with care The stated total is derived from the units and the duration, so a rule has to recompute it and compare. | The stated power is a field in the request, compared with the computed one on every call. |
| Every problem returned in one answer | Only with workarounds Rules tend to fire as the project is saved or a step is completed, so a person often fixes one error and meets the next. | All findings come back together, whatever order the choices arrived in. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | The project has 0 B-VAULT units; at least 1 is needed. |
| 2 | The project needs 25,000 kW of power; 0 units give 0 kW at this duration. |
| 3 | The project needs 50,000 kWh of energy; 0 units give 0 kWh. |
| 4 | The datasheet gives system power for 2-hour and 4-hour discharge only; 3 hours is not one of them. |
| 5 | The datasheet gives system power for 2-hour and 4-hour discharge only; 1 hour is not one of them. |
| 6 | The project needs 29,821 kW of power; 20 units give 29,820 kW at this duration. |
| 7 | The project needs 59,641 kWh of energy; 20 units give 59,640 kWh. |
| 8 | The project needs 25,000 kW of power; 20 units give 14,900 kW at this duration. |
| 9 | The site reaches 46 degrees Celsius; this coupling is rated to 45 degrees. |
| 10 | The site reaches 51 degrees Celsius; this coupling is rated to 50 degrees. |
| 11 | The site falls to -21 degrees Celsius; the rated range starts at minus 20 degrees. |
| 12 | The inverter DC voltage of 1,099 volts is outside the 1,100 to 1,500 volt window of the DC-coupled system. |
| 13 | The inverter DC voltage of 1,501 volts is outside the 1,100 to 1,500 volt window of the DC-coupled system. |
| 14 | Energy Vault maintains a list of inverter models compatible with the DC-coupled B-VAULT and does not publish it; a person should confirm the inverter is on it. |
| 15 | The datasheet says the system is de-rated over 3,000 meters; the site is at 3,001 meters, so a person should confirm the de-rating. |
| 16 | The project states 29,819 kW of power; the units give 29,820 kW. |
| 17 | The project states 29,821 kW of power; the units give 29,820 kW. |
| 18 | The project needs 300,000 kW of power; 200 units give 298,200 kW at this duration. |
| 19 | The project needs 25,000 kW of power; 10 units give 7,450 kW at this duration. |
| 20 | The project needs 50,000 kWh of energy; 10 units give 29,820 kWh. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Please quote 20 B-VAULT units, AC-coupled, with a 2-hour discharge, for a project that needs 30,000 kW of power and 60,000 kWh of energy. The site reaches 38 degrees Celsius in summer and falls to -10 degrees in winter, at an altitude of 300 meters. The project states 30,000 kW of power in total. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote 21 B-VAULT units, AC-coupled, with a 2-hour discharge, for a project that needs 30,000 kW of power and 60,000 kWh of energy. The site reaches 38 degrees Celsius in summer and falls to -10 degrees in winter, at an altitude of 300 meters. The project states 31,311 kW of power in total. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote 16 B-VAULT units, AC-coupled, with a 4-hour discharge, for a project that needs 11,000 kW of power and 45,000 kWh of energy. The site reaches 47 degrees Celsius in summer and falls to 2 degrees in winter, at an altitude of 900 meters. The project states 11,920 kW of power in total. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote 16 B-VAULT units, DC-coupled, with a 4-hour discharge, for a project that needs 11,000 kW of power and 45,000 kWh of energy. The site reaches 47 degrees Celsius in summer and falls to 2 degrees in winter, at an altitude of 900 meters. The customer inverter has a DC voltage of 1,300 volts and its model is on the list of inverters Energy Vault has confirmed as compatible. The project states 11,920 kW of power in total. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote 24 B-VAULT units, DC-coupled, with a 2-hour discharge, for a project that needs 35,000 kW of power and 70,000 kWh of energy. The site reaches 40 degrees Celsius in summer and falls to -15 degrees in winter, at an altitude of 1,200 meters. The customer inverter has a DC voltage of 1,650 volts and its model is not on the list of inverters Energy Vault has confirmed as compatible. The project states 35,784 kW of power in total. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote 24 B-VAULT units, DC-coupled, with a 2-hour discharge, for a project that needs 35,000 kW of power and 70,000 kWh of energy. The site reaches 40 degrees Celsius in summer and falls to -15 degrees in winter, at an altitude of 1,200 meters. The customer inverter has a DC voltage of 1,400 volts and its model is not on the list of inverters Energy Vault has confirmed as compatible. The project states 35,784 kW of power in total. It is ready to send.
Verdict: Needs approval.
The agent's request. Please quote 24 B-VAULT units, DC-coupled, with a 2-hour discharge, for a project that needs 35,000 kW of power and 70,000 kWh of energy. The site reaches 40 degrees Celsius in summer and falls to -15 degrees in winter, at an altitude of 1,200 meters. The customer inverter has a DC voltage of 1,400 volts and its model is on the list of inverters Energy Vault has confirmed as compatible. The project states 35,784 kW of power in total. It is ready to send.
Verdict: Allowed.