Predictika · Electrical equipment orders: molded case circuit breakers
An AI sales agent puts together an order for an HGM-type molded case circuit breaker from HYUNDAI ELECTRIC's HG-Series catalog: the frame and type, the rated current, the pole count, the short-circuit current and load at the site, the cabinet temperature and altitude, and the accessories. Before it goes out, the agent sends the order to Predictika, which checks it against a declarative model of the published tables and returns a verdict, every reason and the figures it computed.
This validator models orders for one product line, the HGM-type breakers in the public HYUNDAI ELECTRIC HG-Series MCCB and ELCB catalog, using its selection, derating and accessory tables, not just the scenarios shown below.
Any order for these breakers that touches these rules is in scope — not only the scenarios pictured here. Not covered: prices (the catalog has none, so this validator produces no price build-up or line-item quote), earth leakage breakers and other series, trip-curve and coordination studies, cable and busbar sizing, and the 4-pole neutral arrangements beyond what the catalog lists.
7 scenarios in 3 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| Breaking capacity that depends on frame, type and voltage | Only with care Each frame and type has six voltage ratings; that is a grid of numbers to load and keep in step with the catalog, and a missed cell lets an under-rated breaker through. | The rating is looked up from the frame, type and voltage on every call and compared with the fault current. |
| A current rating that falls with temperature | Only with workarounds The current a breaker carries drops as the cabinet gets hotter, by a different curve for each frame group; a rule has to read the temperature and the frame together, which a single rated-current attribute cannot express. | The carrying current is computed from the frame, rating and temperature, then compared with the load. |
| Accessories that exist on some frames and pole counts only | Only with care The motor operator, interlock, terminal extensions and DIN adapter each have their own list of frames and poles; each is a separate rule keyed to a model list. | Frame, poles and accessories are in one request and checked together. |
| Stated figures that disagree with the catalog | Only with care The figures the agent states are free-entry fields; a rule can compare them with the catalog, but only if someone writes and maintains it for every frame. | The stated figures travel with the order and are compared with the computed ones on every call. |
| Every problem returned in one answer | Only with workarounds Rules tend to fire as the order is saved or a step is completed, so a rep often fixes one error and meets the next. | All findings come back together, whatever order the choices arrived in. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | The prospective short-circuit current of 20.5 kA is above the 20.0 kA rated ultimate breaking capacity (Icu) of the selected type at this voltage. |
| 2 | The prospective short-circuit current of 38.5 kA is above the 38.0 kA rated ultimate breaking capacity (Icu) of the selected type at this voltage. |
| 3 | The short-circuit current of 28.0 kA is above the 15.0 kA service breaking capacity (Ics) of this type, though within its ultimate capacity (Icu); the breaker may need replacing after such a fault, so a person should confirm. |
| 4 | The short-circuit current of 30.0 kA is above the 15.0 kA service breaking capacity (Ics) of this type, though within its ultimate capacity (Icu); the breaker may need replacing after such a fault, so a person should confirm. |
| 5 | The prospective short-circuit current of 31.0 kA is above the 30.0 kA rated ultimate breaking capacity (Icu) of the selected type at this voltage. |
| 6 | The short-circuit current of 19.6 kA is above the 19.5 kA service breaking capacity (Ics) of this type, though within its ultimate capacity (Icu); the breaker may need replacing after such a fault, so a person should confirm. |
| 7 | The selected type code is not offered on this frame: the HGM30 is listed with the E and S types only, and the HGM800 with the S, H and L types. |
| 8 | A rated current of 70 A is not offered on the selected frame. |
| 9 | A rated current of 63 A is not offered on the selected frame. |
| 10 | A rated current of 400 A is not offered on the selected frame. |
| 11 | The selected current-setting dial is not offered on this frame: 32 to 250 AF frames adjust to 80, 90 or 100 percent of the rated current, and 400 to 800 AF frames to 63, 80 or 100 percent. |
| 12 | The DC 250 V breaking capacity is listed for 2-pole breakers only; the order has 3 poles. |
| 13 | The prospective short-circuit current of 10.5 kA is above the 10.0 kA rated ultimate breaking capacity (Icu) of the selected type at this voltage. |
| 14 | The load current of 80.5 A is above the 80.0 A that the breaker carries at its current-setting dial. |
| 15 | The ambient temperature of 71 degrees C is above the 70 degrees C limit of the catalog derating table. |
| 16 | The load current of 104.0 A is above the 100.0 A that the breaker carries at its current-setting dial. |
| 17 | At the site ambient temperature the breaker is rated 97.6 A, below the load current of 97.7 A. |
| 18 | At the site ambient temperature the breaker is rated 98.0 A, below the load current of 99.0 A. |
| 19 | Plug-in types are listed for 3-pole breakers only (the 2-row TDA type also for 2 poles on the HGM30, HGM50 E/S, HGM60 and HGM100); the order has 4 poles. |
| 20 | Plug-in types are listed for 3-pole breakers only (the 2-row TDA type also for 2 poles on the HGM30, HGM50 E/S, HGM60 and HGM100); the order has 2 poles. |
| 21 | The TDF and TDA plug-in types are listed up to 125 AF; the 160 AF and larger frames take the TDM types only. |
| 22 | At the site altitude the breaker carries 96.0 A, below the load current of 97.0 A. |
| 23 | At the site altitude of 3000 m the maximum operational voltage of the breaker is 590 V, below the system voltage. |
| 24 | At the site altitude of 5000 m the maximum operational voltage of the breaker is 460 V, below the system voltage. |
| 25 | The site altitude of 5001 m is above the 5,000 m limit of the catalog altitude table. |
| 26 | A protected neutral pole is needed, but the 4-pole arrangement listed is 4P3D, whose neutral pole is unprotected; a 4P4D arrangement is not offered. |
| 27 | The motor operator is listed for 3-pole and 4-pole breakers only; the order has 2 poles. |
| 28 | On the 160 AF and larger frames the mechanical interlock is listed for 3-pole and 4-pole breakers only; the order has 2 poles. |
| 29 | Terminal extensions (busbars) are listed for the 160 AF and larger frames only. |
| 30 | The DIN rail adapter is listed for the HGM30, HGM50 E/S, HGM60 and HGM100 only. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Please quote an HD Hyundai Electric HGM100 type S molded case circuit breaker, 3 poles, rated 100 A, at 380 V. The site has a prospective short-circuit current of 25 kA and a load of 80 A, in a cabinet at 40 degrees C at 1,000 m altitude. The quote states a breaking capacity of 30 kA and a carrying current of 100 A at the site temperature. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote an HD Hyundai Electric HGM125 type S molded case circuit breaker, 3 poles, rated 125 A, at 380 V. The site has a prospective short-circuit current of 25 kA and a load of 80 A, in a cabinet at 40 degrees C at 1,000 m altitude. The quote states a breaking capacity of 26 kA and a carrying current of 125 A at the site temperature. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote an HD Hyundai Electric HGM100 type S molded case circuit breaker, 3 poles, rated 100 A, at 380 V. The site has a prospective short-circuit current of 15 kA and a load of 99 A, in a cabinet at 60 degrees C at 1,000 m altitude. The quote states a breaking capacity of 20 kA and a carrying current of 100 A at the site temperature. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote an HD Hyundai Electric HGM125 type S molded case circuit breaker, 3 poles, rated 125 A, at 380 V. The site has a prospective short-circuit current of 15 kA and a load of 99 A, in a cabinet at 60 degrees C at 1,000 m altitude. The quote states a breaking capacity of 26 kA and a carrying current of 117.2 A at the site temperature. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote an HD Hyundai Electric HGM125 type S molded case circuit breaker, 2 poles, rated 125 A, at 380 V. The site has a prospective short-circuit current of 15 kA and a load of 90 A, in a cabinet at 40 degrees C at 1,000 m altitude. It needs a motor operator and a DIN rail adapter. The quote states a breaking capacity of 26 kA and a carrying current of 125 A at the site temperature. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote an HD Hyundai Electric HGM100 type S molded case circuit breaker, 2 poles, rated 100 A, at 380 V. The site has a prospective short-circuit current of 15 kA and a load of 90 A, in a cabinet at 40 degrees C at 1,000 m altitude. It needs a motor operator and a DIN rail adapter. The quote states a breaking capacity of 20 kA and a carrying current of 100 A at the site temperature. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote an HD Hyundai Electric HGM100 type S molded case circuit breaker, 3 poles, rated 100 A, at 380 V. The site has a prospective short-circuit current of 15 kA and a load of 90 A, in a cabinet at 40 degrees C at 1,000 m altitude. It needs a motor operator and a DIN rail adapter. The quote states a breaking capacity of 20 kA and a carrying current of 100 A at the site temperature. It is ready to send.
Verdict: Allowed.
The text of the narrated walkthrough, step by step.