Predictika · Electrical protection equipment
An AI sales agent prepares a quote for a Havells HIM moulded case circuit breaker: frame, poles, rated current, breaking class, voltage, internal accessories and trip coil voltage. Before it goes out, the agent sends it to Predictika, which checks it against a declarative model of Havells' published HIM catalogue and returns a verdict, every reason and the figures it looked up.
This validator models quotes for the Havells HIM moulded case circuit breaker range in the catalogue, not just the scenarios shown below.
Any HIM breaker quote that touches these rules is in scope — not only the scenarios pictured here. Not covered: prices (the catalogue has none, so this validator produces no price build-up or line-item quote), the Loadline series and other Havells ranges, residual current and motor protection releases, mounting and terminal accessories, and dimensions. Assumptions: the catalogue shows allowed internal accessory combinations as icon diagrams and this validator reads them as printed; a combination not shown is blocked, and a breaker class and voltage not listed gives no capacity.
6 scenarios in 3 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| Breaking capacity by frame, class and voltage | Only with workarounds Capacity depends on three things at once, and a rules-based CPQ needs a table of option rules per frame and class that someone has to keep in step with the catalogue. | The frame, class and voltage travel in one request and the capacity is looked up and compared with the site fault level on every call. |
| Which accessories fit which frame and pole count | Only with care Accessory combinations differ by frame and poles, so each frame needs its own cross-line rules and an exception for each new accessory. | The frame, poles and accessories are in one request and checked together. |
| Trip coil voltages per frame | Only with workarounds Each coil voltage is offered on some frames and not others, so the coil choice needs its own rule per frame. | The coil and frame are checked together against the catalogue lists. |
| Every problem returned in one answer | Only with workarounds Rules tend to fire as the quote is saved or a step is completed, so a rep often fixes one error and meets the next. | All findings come back together, whatever order the choices arrived in. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | The HIM250 frame is not offered with 2 poles in the catalogue. |
| 2 | The HIM400 frame is not offered with 2 poles in the catalogue. |
| 3 | A rated current of 125 A is not offered for the HIM100 frame. |
| 4 | A rated current of 100 A is not offered for the HIM250 frame. |
| 5 | A rated current of 630 A is not offered for the HIM400 frame. |
| 6 | Breaking class E is not offered for the HIM125 frame. |
| 7 | Breaking class L is not offered for the HIM100 frame. |
| 8 | Breaking class E is not offered for the HIM800 frame. |
| 9 | The site fault level of 20.0 kA is above the 16.0 kA breaking capacity (Icu) of this breaker at this voltage. |
| 10 | The site fault level of 30.0 kA is above the 26.0 kA breaking capacity (Icu) of this breaker at this voltage. |
| 11 | The site fault level of 86.0 kA is above the 85.0 kA breaking capacity (Icu) of this breaker at this voltage. |
| 12 | The site fault level of 11.0 kA is above the 10.0 kA breaking capacity (Icu) of this breaker at this voltage. |
| 13 | The order states a breaking capacity of 42.0 kA but the catalogue lists 38.0 kA for this breaker at this voltage. |
| 14 | The auxiliary + alarm switch (AXT) is not offered for the HIM400 frame. |
| 15 | The DIN rail adaptor is offered for the HIM100 frame only, not for the HIM125 frame. |
| 16 | This combination of internal accessories is not among the combinations shown in the catalogue for the HIM100 frame with 2 poles. |
| 17 | This combination of internal accessories is not among the combinations shown in the catalogue for the HIM100 frame with 3 poles. |
| 18 | This combination of internal accessories is not among the combinations shown in the catalogue for the HIM250 frame with 3 poles. |
| 19 | The 48 Vdc trip coil voltage is not offered for the shunt or undervoltage trip on the HIM400 frame. |
| 20 | The 100-125 Vdc trip coil voltage is not offered for the shunt or undervoltage trip on the HIM100 frame. |
| 21 | The site fault level of 40.0 kA is above the 10.0 kA breaking capacity (Icu) of this breaker at this voltage. |
| 22 | The order states a breaking capacity of 20.0 kA but the catalogue lists 10.0 kA for this breaker at this voltage. |
| 23 | The DIN rail adaptor is offered for the HIM100 frame only, not for the HIM250 frame. |
| 24 | This combination of internal accessories is not among the combinations shown in the catalogue for the HIM250 frame with 2 poles. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Please quote a Havells HIM125 100 A, 3-pole, class E breaker at 415 V for a panel with a 30 kA fault level. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a Havells HIM125 100 A, 3-pole, class H breaker at 415 V for a panel with a 30 kA fault level. The breaking capacity of this breaker is 38 kA. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a Havells HIM100 63 A, 2-pole, class S breaker at 415 V for a panel with a 10 kA fault level, with an auxiliary switch and an alarm switch. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a Havells HIM100 63 A, 2-pole, class S breaker at 415 V for a panel with a 10 kA fault level, with an auxiliary switch. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a Havells HIM400 400 A, 3-pole, class E breaker at 415 V for a panel with a 50 kA fault level, with an auxiliary + alarm switch (AXT). The breaking capacity of this breaker is 45 kA. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a Havells HIM400 400 A, 3-pole, class S breaker at 415 V for a panel with a 50 kA fault level, with an auxiliary switch, an alarm switch and a shunt trip. The breaking capacity of this breaker is 65 kA. The trip coil is 100-125 Vdc. It is ready to send.
Verdict: Allowed.
The text of the narrated walkthrough, step by step.