Predictika · Distribution transformer orders
An AI sales agent prepares an order for an oil-immersed or dry-type distribution transformer: rating, highest voltage, winding options, the loss levels it promises and, for dry-type, the test voltages and thermal alarm. Before it goes out, the agent sends it to Predictika, which checks it against a declarative model of the published KONČAR documents and returns a verdict, every reason and the figures it looked up.
This validator models distribution transformer orders against KONČAR's public Ecodesign brochure, distribution transformer brochure and dry-type brochure, not just the scenarios shown below.
Any order for these transformers that touches these rules is in scope — not only the scenarios pictured here. Not covered: prices (KONČAR publishes no price list, so this validator produces no price build-up or line-item quote), the numeric loss limits in watts, which are in the EU regulation and not in the documents read, and power transformers above 8000 kVA.
6 scenarios in 3 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| Loss class and tier together decide what is allowed | Only with workarounds The no-load margin, the load class and the minimum efficiency all depend on type, rating band and tier at once, so each needs its own lookup keyed on the combination. | Type, rating and tier are in one request and the requirement is looked up from the combination on every call. |
| A stated uplift that must equal the correction table | Only with care The uplift is a free-entry figure; a rule can compare it with a looked-up value, but someone has to write and maintain that comparison for every winding option. | The stated figures travel with the order and are compared with the looked-up figures on every call. |
| Test voltages and alarm temperature that follow the voltage and insulation class | Only with care The expected value depends on the highest voltage or the insulation class, so each check needs a lookup keyed on that field. | The expected test voltages and alarm temperature are looked up from the voltage and insulation class and compared with the quote. |
| Documents that disagree (dry-type range) | Only with workarounds A rules table normally holds one limit; two published limits need a middle band that is neither allowed nor refused. | The band between the two published limits is flagged for confirmation instead of being allowed or refused. |
| Every problem returned in one answer | Only with workarounds Rules tend to fire as the order is saved or a step is completed, so a rep often fixes one error and meets the next. | All findings come back together, whatever order the choices arrived in. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | The quoted peak efficiency index is 99531 but the minimum for this rating and tier is 99532 (the index is given in thousandths of a percent). |
| 2 | The quoted peak efficiency index is 99509 but the minimum for this rating and tier is 99510 (the index is given in thousandths of a percent). |
| 3 | The quoted peak efficiency index is 99483 but the minimum for this rating and tier is 99548 (the index is given in thousandths of a percent). |
| 4 | The rating lies between ratings in the peak efficiency table; the minimum is obtained by interpolation and is not computed here. |
| 5 | A rated power of 8500 kVA is outside the published range for this transformer type (oil-immersed 50 to 8000 kVA; dry-type up to 5000 kVA). |
| 6 | A rated power of 40 kVA is outside the published range for this transformer type (oil-immersed 50 to 8000 kVA; dry-type up to 5000 kVA). |
| 7 | A rated power of 6300 kVA is outside the published range for this transformer type (oil-immersed 50 to 8000 kVA; dry-type up to 5000 kVA). |
| 8 | KONČAR documents give the dry-type range as up to 3150 kVA on its website and up to 5000 kVA in its brochures, so a rating in between needs confirmation. |
| 9 | Dry-type distribution transformers are published for a highest voltage for equipment up to 24 kV; 36 kV is for oil-immersed transformers. |
| 10 | The quoted no-load losses do not meet the Ecodesign requirement for this type, rating and tier (class A0, and 10 percent below the A0 level from Tier 2). |
| 11 | The quoted load losses are above the Ecodesign limit for this type, rating and tier, which is class Bk. |
| 12 | The quoted load losses are above the Ecodesign limit for this type, rating and tier, which is class Ak. |
| 13 | The quote states loss-limit uplifts of 20 percent (no-load) and 10 percent (load), but the Ecodesign correction table gives 20 and 15 percent. |
| 14 | The quote states loss-limit uplifts of 20 percent (no-load) and 5 percent (load), but the Ecodesign correction table gives 10 and 5 percent. |
| 15 | With dual voltage on one winding at reduced power, the maximum power on the lower voltage is 85 percent of the rating at the higher voltage; the quote asks for 100 percent. |
| 16 | The selected winding feature does not match the highest voltage for equipment on the quote (the 36 kV rows apply to Um = 36 kV, the other row to Um of 24 kV or less). |
| 17 | The quote states test voltages of 50 kV (power frequency) and 95 kV (lightning impulse), but the dry-type brochure gives 28 and 75 kV for this highest voltage for equipment. |
| 18 | The quote sets the thermal-protection alarm at 135 C, but the dry-type brochure gives 160 C for this insulation temperature class. |
| 19 | The dry-type brochure bases ratings on a 40 C maximum ambient and an altitude up to 1000 m; higher values must be specified in the enquiry and confirmed. |
| 20 | Rectifier, furnace, offshore, earthing and railway transformers are engineered to order and are outside the EU Ecodesign Regulation; KONČAR publishes no ratings or options for them, so none are checked. |
| 21 | The quote states test voltages of 50 kV (power frequency) and 125 kV (lightning impulse), but the dry-type brochure gives 50 and 95 kV for this highest voltage for equipment. |
| 22 | The quote sets the thermal-protection alarm at 150 C, but the dry-type brochure gives 135 C for this insulation temperature class. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Please quote a 1000 kVA oil-immersed distribution transformer, highest voltage for equipment 24 kV, standard windings, Tier 2. The quote promises no-load losses at class A0 with a 0 percent margin and load losses at class Ak, and it states loss-limit uplifts of 0 percent (no-load) and 0 percent (load). It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a 1000 kVA oil-immersed distribution transformer, highest voltage for equipment 24 kV, standard windings, Tier 2. The quote promises no-load losses at class A0 with a 10 percent margin and load losses at class Ak, and it states loss-limit uplifts of 0 percent (no-load) and 0 percent (load). It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a 1000 kVA oil-immersed distribution transformer, highest voltage for equipment 36 kV, 36 kV primary with secondary over 1.1 kV, Tier 2. The quote promises no-load losses at class A0 with a 10 percent margin and load losses at class Ak, and it states loss-limit uplifts of 20 percent (no-load) and 10 percent (load). It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a 1000 kVA oil-immersed distribution transformer, highest voltage for equipment 36 kV, 36 kV primary with secondary over 1.1 kV, Tier 2. The quote promises no-load losses at class A0 with a 10 percent margin and load losses at class Ak, and it states loss-limit uplifts of 20 percent (no-load) and 15 percent (load). It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a 800 kVA dry-type distribution transformer, highest voltage for equipment 12 kV, standard windings, Tier 2. The quote promises no-load losses at class A0 with a 10 percent margin and load losses at class Ak, and it states loss-limit uplifts of 0 percent (no-load) and 0 percent (load). The dry-type unit is insulation class H with the thermal alarm set at 135 C, and the quote gives test voltages of 50 kV power frequency and 95 kV lightning impulse. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a 800 kVA dry-type distribution transformer, highest voltage for equipment 12 kV, standard windings, Tier 2. The quote promises no-load losses at class A0 with a 10 percent margin and load losses at class Ak, and it states loss-limit uplifts of 0 percent (no-load) and 0 percent (load). The dry-type unit is insulation class H with the thermal alarm set at 160 C, and the quote gives test voltages of 28 kV power frequency and 75 kV lightning impulse. It is ready to send.
Verdict: Allowed.
The text of the narrated walkthrough, step by step.