Predictika · Circuit protection · Fuses
An AI sales agent prepares an order for Mersen Amp-Trap fuses: the series, the ampere size, the fuse holder, and the circuit it protects, with its voltage, available fault current, load and conductor. Before it goes out, the agent sends it to Predictika, which checks it against a declarative model of fuse selection rules and returns a verdict, every reason and the figures it computed.
This validator models an order for 10 Amp-Trap fuse series for a circuit, not just the scenarios shown below.
Any order for these series that touches these rules is in scope — not only the scenarios pictured here. Not covered: prices (this page shows no price build-up), fuse holders and blocks as separate products, other Mersen product lines such as photovoltaic (gPV), high-speed and Class L variants not listed, and coordination studies.
7 scenarios in 3 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| Voltage, ampere and interrupting limits that differ for each of 10 fuse series | Only with workarounds Every series has its own AC and DC voltage, ampere range, standard sizes and interrupting rating. A rules-based CPQ needs a table or a set of rules per series, and a catalog update means editing each of them. | The series arrives in one request and every limit for it is looked up and checked together. |
| Several problems in one order, such as a fast-acting fuse on a motor, in the wrong holder, above the conductor | Only with workarounds Rules tend to fire as the order is saved or a step is completed, so a person often fixes one error and meets the next. | All findings come back together, whatever order the choices arrived in. |
| The load and conductor the fuse protects | Only with care The 80 percent continuous load rule, conductor protection and motor sizing need arithmetic on fields the order carries, with a next-size-up allowance that goes to a person. | The load, conductor and fuse size are fields in the request and are compared on every call. |
| Holder class that must match the series | Only with care A compatibility table between each series and each holder class has to be kept up to date. | The holder is checked against the series in the same request. |
| Total number of fuses the order states | Only with care The stated total is derived from circuits and poles, so a rule has to recompute it and compare. | The stated total is a field in the request, compared with the computed one on every call. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | The order has 0 circuits of 3 poles; at least 1 of each is needed. |
| 2 | The circuit is 690 volts AC; this fuse series is rated 600 volts AC. |
| 3 | The circuit is 480 volts AC; this fuse series is rated 250 volts AC. |
| 4 | The circuit is 600 volts DC; this fuse series is rated 500 volts DC (0 means not rated for DC). |
| 5 | The circuit is 480 volts DC; this fuse series is rated 0 volts DC (0 means not rated for DC). |
| 6 | This fuse series is made from 1 to 600 amperes; the order is for 700 amperes. |
| 7 | 85 amperes is not a standard ampere size for this fuse series. |
| 8 | This fuse series is made from 1 to 30 amperes; the order is for 40 amperes. |
| 9 | This fuse does not fit the selected fuse holder class. |
| 10 | The available fault current is 250 kA; this fuse is rated to interrupt 200 kA. |
| 11 | The available fault current is 120 kA; this fuse is rated to interrupt 100 kA. |
| 12 | The load of 90 amperes is more than 80 percent of the 100 ampere fuse. |
| 13 | The fuse is above the conductor ampacity but within 25 percent; a person should confirm the next standard size allowance for this conductor. |
| 14 | The 150 ampere fuse is too far above the 100 ampere conductor to protect it. |
| 15 | A fast-acting fuse would open on motor starting current; a time-delay series is needed for a motor. |
| 16 | The time-delay fuse is above 175 percent of the motor full-load current; a person should confirm it for this motor. |
| 17 | The 100 ampere time-delay fuse is more than 225 percent of the 40 ampere motor full-load current. |
| 18 | A fast-acting fuse on a transformer circuit may open on inrush current; a person should confirm it. |
| 19 | A semiconductor load needs a semiconductor fuse series such as the A70QS. |
| 20 | The circuit is 750 volts AC; this fuse series is rated 700 volts AC. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Please quote 12 circuits of 3 poles with A4J200 fuses in Class RK holders, for a motor on a 480 volt AC circuit with 96 amperes of load, a 150 ampere conductor and 65 kA of available fault current. The order states 36 fuses in total. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote 12 circuits of 3 poles with AJT150 fuses in Class J holders, for a motor on a 480 volt AC circuit with 96 amperes of load, a 150 ampere conductor and 65 kA of available fault current. The order states 36 fuses in total. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote 8 circuits of 2 poles with A2D200R fuses in Class RK holders, for a feeder on a 600 volt DC circuit with 140 amperes of load, a 200 ampere conductor and 50 kA of available fault current. The order states 16 fuses in total. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote 8 circuits of 2 poles with AJT200 fuses in Class J holders, for a feeder on a 600 volt DC circuit with 140 amperes of load, a 200 ampere conductor and 50 kA of available fault current. The order states 16 fuses in total. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote 8 circuits of 2 poles with A6D200R fuses in Class RK holders, for a feeder on a 600 volt DC circuit with 140 amperes of load, a 200 ampere conductor and 50 kA of available fault current. The order states 16 fuses in total. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote 6 circuits of 3 poles with AJT150 fuses in Class J holders, for a semiconductor (drive rectifier) load on a 600 volt AC circuit with 100 amperes of load, a 150 ampere conductor and 100 kA of available fault current. The order states 18 fuses in total. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote 6 circuits of 3 poles with A70QS150 fuses in semiconductor fuse block holders, for a semiconductor (drive rectifier) load on a 600 volt AC circuit with 100 amperes of load, a 150 ampere conductor and 100 kA of available fault current. The order states 18 fuses in total. It is ready to send.
Verdict: Allowed.
The text of the narrated walkthrough, step by step.