Predictika · Engineered rooftop, air handler and make-up air units
An AI sales agent prepares an order for an engineered rooftop unit, air handler or indoor make-up air unit from the public Sterling HVAC model number key and parts catalog. Before it goes out, the agent sends it to Predictika, which checks it against a declarative model of those documents and returns a verdict, every reason and the figures it computed.
This validator models orders for the engineered units in two public Sterling HVAC documents (the replacement parts catalog RRPC-7 and the HVAC equipment brochure GACP-26), not just the scenarios shown below.
Any order for these units that touches these rules is in scope — not only the scenarios pictured here. Not covered: prices (Sterling HVAC publishes none for these units, so this validator produces no price build-up or line-item quote), other Sterling or Mestek products, options not listed in these two documents, and any change Sterling has made since the documents were published (the parts catalog is dated 11/08).
8 scenarios in 3 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| An arrangement or furnace type that is not offered for the unit type | Only with care Every unit type has its own arrangement list and its own furnace restrictions, so each combination needs its own rule rows, and a new catalog means editing them by hand. | The unit type, arrangement and furnace are in one request and compared with the catalog on every call. |
| Airflow outside the range for the unit and blower | Only with care The range depends on the unit type and on whether the arrangement uses the standard or the high CFM blower, so the limit has to be looked up per combination. | The range is computed from the unit type and arrangement and compared with the order on every call; the finding shows both numbers. |
| A burner count stated by the agent that does not match the capacity | Only with workarounds The stated figure is usually free text or a separate field, so it takes an extra rule that looks up the catalog count and compares. | The stated figure is part of the request and is compared with the computed figure on every call. |
| Accessories listed for another unit type, and options that overlap | Only with care Each accessory has its own list of unit types, and double wall construction already including hinged doors is easy to miss. | All accessory rules are checked together on every call, in whatever order the choices arrived. |
| Every problem returned in one answer | Only with workarounds Rules tend to fire as a step is completed, so a rep often fixes one error and meets the next. | All findings come back together, whatever order the choices arrived in. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | 450 thousand BTU/h is not a capacity in the model number key; the key lists single furnace 100 to 400, double furnace 500 to 800 and triple furnace 1,200 thousand BTU/h. |
| 2 | This arrangement is not listed for this unit type; RT and PV rooftop units use arrangements A to L, AH air handlers use M to W, and indoor make-up air units use A, B, D, G or K. |
| 3 | The indoor duct arrangement is listed for the 500 and 1,200 thousand BTU/h capacities only, and the order is for 300 thousand BTU/h. |
| 4 | The high temperature rise furnace (60 to 90 F) is listed for separated combustion MS units only, not for MU or ME indoor make-up air units. |
| 5 | The catalog marks the high temperature rise heat exchanger as not available for double and triple furnace rooftop units, and the order has 2 furnace sections. |
| 6 | The model number key lists the high temperature rise furnace for MS units, but the MS parts pages list only furnace types A and B; Sterling should confirm the furnace type. |
| 7 | The catalog marks this mechanical modulation gas control as discontinued in 2,005. |
| 8 | The indoor make-up air key lists only outside air, bottom return air and outside plus return air inlets; the air hood inlets are listed for rooftop units. |
| 9 | Moisture eliminators (A1), through the base utility penetrations (N2) and the rooftop service convenience package (N3) are listed for rooftop and air handler units, not for indoor make-up air units. |
| 10 | The indoor service convenience package (N5) is listed for indoor make-up air units, not for rooftop and air handler units. |
| 11 | The draftor (M1) is listed for the natural vent MU indoor unit only. |
| 12 | The vertical and horizontal concentric vent kits (M4, M5) are listed for the separated combustion MS unit only. |
| 13 | The fan time delay (K4) is listed for arrangement A, the duct furnace, only. |
| 14 | The standard blower module is listed with a 5 HP (184T frame) motor maximum, and the order has a larger motor; motors up to 15 HP are listed with the high CFM blower. |
| 15 | The order calls for 15,000 CFM, but the brochure range for this unit and blower is 800 to 14,000 CFM. |
| 16 | The order calls for 700 CFM, but the brochure range for this unit and blower is 800 to 14,000 CFM. |
| 17 | The order calls for 8,001 CFM, but the brochure range for this unit and blower is 1,500 to 8,000 CFM. |
| 18 | The order calls for 2,000 CFM, but the brochure range for this unit and blower is 3,000 to 15,000 CFM. |
| 19 | The order calls for 9,801 CFM, but the brochure lists airflows up to 9,800 CFM for this unit. |
| 20 | The brochure lists factory assembled coil cabinets on high CFM air handlers up to 20 tons, and the order has 21 tons of coil. |
| 21 | The catalog shows a coil cabinet only in arrangements K and L (rooftop), U and W (air handler) and K (indoor); a coil on another arrangement should be confirmed with Sterling. |
| 22 | The catalog shows evaporative cooling in arrangements D and E (rooftop), P and R (air handler) and D (indoor); evaporative cooler accessories on another arrangement should be confirmed with Sterling. |
| 23 | The catalog lists a standard elevation of 0 to 2,000 feet; the site is at 5,200 feet and the order has neither the high altitude unit (A6) nor the unit de-rate (A8). |
| 24 | Double wall construction (N6) already includes hinged access doors (N1), so the order lists the doors twice; a person should confirm. |
| 25 | The order states 10 main burners in all, but the catalog burner counts for this capacity give 12. |
| 26 | The order states 16 main burners in all, but the catalog burner counts for this capacity give 48. |
| 27 | The catalog lists a standard elevation of 0 to 2,000 feet; the site is at 3,000 feet and the order has neither the high altitude unit (A6) nor the unit de-rate (A8). |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Please quote a Sterling ME indoor make-up air unit, arrangement A, at 300 thousand BTU/h with a high temperature rise furnace, 6,500 CFM and a 3 HP motor, an outside air hood inlet, with double wall construction (N6), hinged access doors (N1). The order states 11 main burners in all. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a Sterling ME indoor make-up air unit, arrangement B, at 300 thousand BTU/h with a standard furnace, 6,500 CFM and a 3 HP motor, with double wall construction (N6). The order states 12 main burners in all. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a Sterling AH air handler unit, arrangement B, at 350 thousand BTU/h with a standard furnace, 9,000 CFM and a 10 HP motor, an outside plus return air inlet. The order states 12 main burners in all. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a Sterling AH air handler unit, arrangement M, at 350 thousand BTU/h with a standard furnace, 9,000 CFM and a 10 HP motor, an outside plus return air inlet. The order states 14 main burners in all. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a Sterling AH air handler unit, arrangement S, at 350 thousand BTU/h with a standard furnace, 9,000 CFM and a 10 HP motor, an outside plus return air inlet. The order states 14 main burners in all. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a Sterling PV rooftop unit, arrangement E, at 600 thousand BTU/h with a high temperature rise furnace, 10,000 CFM and a 5 HP motor, mechanical modulation 75 to 200 F gas control, with concentric vent kit (M4, M5), evaporative cooler kit (C), at a site elevation of 6,000 feet. The order states 24 main burners in all. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a Sterling PV rooftop unit, arrangement E, at 600 thousand BTU/h with a standard furnace, 10,000 CFM and a 5 HP motor, electronic modulation, duct sensing gas control, with evaporative cooler kit (C), at a site elevation of 6,000 feet. The order states 24 main burners in all. It is ready to send.
Verdict: Needs approval.
The agent's request. Please quote a Sterling PV rooftop unit, arrangement E, at 600 thousand BTU/h with a standard furnace, 10,000 CFM and a 5 HP motor, electronic modulation, duct sensing gas control, with evaporative cooler kit (C), high altitude unit (A6), at a site elevation of 6,000 feet. The order states 24 main burners in all. It is ready to send.
Verdict: Allowed.
The text of the narrated walkthrough, step by step.