Predictika · 1.1 kV XLPE single-core power cables
An AI sales agent proposes a single-core XLPE power cable for a circuit: conductor, armour, size, how it is installed, the load and the fault current. Before the quote goes out, the agent sends it to Predictika, which checks it against a declarative model of the rating, derating and short-circuit tables in the published catalogue and returns a verdict, every reason and the figures it computed.
This validator models single-core circuits from Polycab's public XLPE heavy duty cable catalogue (2022), not just the scenarios shown below.
Any single-core circuit that touches these rules is in scope — not only the scenarios pictured here. Not covered: prices (the catalogue publishes none, so this validator produces no price build-up or line-item quote), multi-core cables, grouping factors for circuits that share a route (the catalogue gives none, so these go to an engineer), soil thermal resistivity other than the catalogue's, cable lengths, voltage drop, and other Polycab cable ranges.
7 scenarios in 3 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| A size that is not made in the chosen construction | Only with care A list of allowed sizes per construction; every new construction means editing the lists. | Construction and size are in one request and checked together. |
| A current rating that depends on conductor, size, installation and number of cables | Only with care A large lookup table maintained by hand, one entry per combination. | The rating is read from the model on every call and compared with the figure the agent stated. |
| A temperature derating that changes the usable current | Only with workarounds The derated figure has to be calculated by a formula or script outside the product rules. | The derated rating is computed and the load is checked against it. |
| A fault current that must stay below a size-dependent short-circuit rating | Only with workarounds The duration scaling is a calculation; a simple rule can compare only fixed values. | The short-circuit rating is scaled for the fault duration and compared in one pass. |
| Every problem returned in one answer | Only with workarounds Rules tend to fire as the quote is saved or a step is completed, so a rep often fixes one error and meets the next. | All findings come back together, whatever order the choices arrived in. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | The circuit carries 220 A, but the cable can carry only 212.03 A at this site temperature. |
| 2 | The circuit carries 213 A, but the cable can carry only 212.03 A at this site temperature. |
| 3 | The circuit carries 290 A, but the cable can carry only 269.67 A at this site temperature. |
| 4 | 20 sq mm is not a size in the Polycab 1.1 kV single-core XLPE range (4 to 1,000 sq mm in the standard steps). |
| 5 | This armour construction is not made at 6 sq mm; round-wire armoured single-core cables start at 10 sq mm and flat-strip armoured at 95 sq mm. |
| 6 | This armour construction is not made at 70 sq mm; round-wire armoured single-core cables start at 10 sq mm and flat-strip armoured at 95 sq mm. |
| 7 | The cable is rated for AC up to 1,100 V and DC up to 1,500 V to earth; the circuit is 1,200 V. |
| 8 | The cable is rated for AC up to 1,100 V and DC up to 1,500 V to earth; the circuit is 1,600 V. |
| 9 | The catalogue gives rating factors only for ambient air 25 to 60 C and ground 15 to 50 C in 5 degree steps; 42 C is not in the table. |
| 10 | The catalogue gives rating factors only for ambient air 25 to 60 C and ground 15 to 50 C in 5 degree steps; 20 C is not in the table. |
| 11 | The quote states a catalogue rating of 260 A, but the catalogue rating for this cable and installation is 233 A. |
| 12 | The quote states a catalogue rating of 212 A, but the catalogue rating for this cable and installation is 233 A. |
| 13 | A fault of 14,000 A lasting 1 s exceeds the cable; its short-circuit rating is 13,590 A for 1 s, falling with the square root of the duration. |
| 14 | A fault of 8,000 A lasting 4 s exceeds the cable; its short-circuit rating is 13,590 A for 1 s, falling with the square root of the duration. |
| 15 | A fault of 8,000 A lasting 1 s exceeds the cable; its short-circuit rating is 6,620 A for 1 s, falling with the square root of the duration. |
| 16 | 2 circuits share the route, but the catalogue ratings are for a single circuit and the catalogue gives no grouping factors; an engineer must confirm the rating. |
| 17 | The circuit carries 300 A, but the cable can carry only 233.0 A at this site temperature. |
| 18 | The quote states a catalogue rating of 200 A, but the catalogue rating for this cable and installation is 195 A. |
| 19 | A fault of 14,000 A lasting 1 s exceeds the cable; its short-circuit rating is 10,020 A for 1 s, falling with the square root of the duration. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Please quote a copper round-wire armoured single-core XLPE cable, 70 sq mm, buried in the ground at 40 C. The circuit carries 230 A and the fault level is 9,000 A for 1 s. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a copper round-wire armoured single-core XLPE cable, 120 sq mm, buried in the ground at 40 C. The circuit carries 230 A and the fault level is 9,000 A for 1 s. The catalogue rating is 295 A. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a aluminium flat-strip armoured single-core XLPE cable, 70 sq mm, in free air at 40 C. The circuit carries 150 A and the fault level is 12,000 A for 1 s. The catalogue rating is 170 A. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a aluminium flat-strip armoured single-core XLPE cable, 95 sq mm, in free air at 40 C. The circuit carries 150 A and the fault level is 12,000 A for 1 s. The catalogue rating is 235 A. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a aluminium flat-strip armoured single-core XLPE cable, 185 sq mm, in free air at 40 C. The circuit carries 150 A and the fault level is 12,000 A for 1 s. The catalogue rating is 366 A. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a copper round-wire armoured single-core XLPE cable, 6 sq mm, in a duct at 30 C. The circuit carries 55 A and the fault level is 500 A for 1 s. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a copper round-wire armoured single-core XLPE cable, 10 sq mm, in a duct at 30 C. The circuit carries 55 A and the fault level is 500 A for 1 s. The catalogue rating is 70 A. It is ready to send.
Verdict: Allowed.