Predictika · Medium-voltage switchgear: metal-clad lineup ratings, cooling and housing
An AI sales agent prepares a lineup for metal-clad medium-voltage switchgear: the voltage class, the breaker current rating, the short-circuit rating, cooling, the one-high or two-high arrangement, arc-resistant construction and the housing. Before it goes out, the agent sends it to Predictika, which checks it against a declarative model of the published PowlVac ratings and returns a verdict, every reason and the figures it computed.
This validator models lineups of one product line, Powell PowlVac metal-clad switchgear (5 kV, 15 kV and 38 kV classes), not just the scenarios shown below.
Any PowlVac lineup in these three classes that touches these rules is in scope — not only the scenarios pictured here. Not covered: prices (Powell does not publish switchgear prices, so this validator produces no price build-up or line-item quote), other Powell switchgear lines, protection and control equipment, bus and cable arrangements, enclosure dimensions, and the 38 kV 31.5 kA alternative that appears in one data sheet.
7 scenarios in 3 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| Ratings that differ by voltage class | Only with care Each class has its own list of current and short-circuit ratings and its own impulse level, so each needs a per-class rule that must stay in step with the documentation. | The class and every rating arrive together and each is checked against the class on every call. |
| A rating that needs an accessory: 4000 A needs cooling fans | Only with workarounds The condition sits on the breaker line and the fans on another, so it needs a cross-line rule that interacts with the other ratings. | Breakers and fans are in one request, and the dependency is checked with everything else. |
| A derate that depends on construction and arrangement | Only with workarounds The 2900 A limit applies only to arc-resistant, two-high lineups with a 3000 A breaker, so it depends on three choices at once. | Construction, arrangement and rating are in one request, and the limit is checked against what the customer needs. |
| Stated impulse level that must match the class | Only with care A stated figure is a free-entry field; a rule can compare it with the class value, but someone has to write and maintain that comparison. | The stated figure travels with the lineup and is compared with the computed value on every call. |
| Every problem returned in one answer | Only with workarounds Rules tend to fire as the order is saved or a step is completed, so a rep often fixes one error and meets the next. | All findings come back together, whatever order the choices arrived in. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | A 4000 A rating is fan cooled, and compartment-mounted forced air cooling fans are required above 3000 A; the quote has no cooling fans. |
| 2 | The quoted rating is 3000 A; 38 kV class switchgear is rated 1200 or 2000 A. |
| 3 | The customer needs 2500 A continuous; the quoted breaker rating is 2000 A. |
| 4 | The quoted continuous current rating is 1500 A; PowlVac breakers are rated 1200, 2000, 3000 or 4000 A. |
| 5 | The customer needs 1500 A continuous; the quoted breaker rating is 1200 A. |
| 6 | The quoted short-circuit rating is 25 kA, which is not one of the ratings listed for this voltage class (5 kV: 36, 50 or 63 kA; 15 kV: 25, 36, 50 or 63 kA; 38 kV: 40 kA). |
| 7 | The quoted short-circuit rating is 40 kA, which is not one of the ratings listed for this voltage class (5 kV: 36, 50 or 63 kA; 15 kV: 25, 36, 50 or 63 kA; 38 kV: 40 kA). |
| 8 | The quoted short-circuit rating is 50 kA, which is not one of the ratings listed for this voltage class (5 kV: 36, 50 or 63 kA; 15 kV: 25, 36, 50 or 63 kA; 38 kV: 40 kA). |
| 9 | The available fault current is 55 kA; the quoted short-circuit rating is 50 kA. |
| 10 | The available fault current is 64 kA; the quoted short-circuit rating is 63 kA. |
| 11 | 38 kV PowlVac switchgear is for indoor installation only; for an outdoor site it must be housed in a Power Control Room, and the quote has none. |
| 12 | The lineup is for an outdoor site; a person should confirm the outdoor housing for this voltage class. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Please quote a 15 kV PowlVac arc-resistant (Type 2B) lineup in a two-high arrangement, with 3,000 A breakers rated 40 kA, for a customer that needs 2,950 A continuous and has 50 kA of fault current available. The quote states a basic impulse level of 60 kV. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a 15 kV PowlVac arc-resistant (Type 2B) lineup in a one-high arrangement, with 3,000 A breakers rated 63 kA, for a customer that needs 2,950 A continuous and has 50 kA of fault current available. The quote states a basic impulse level of 95 kV. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a 38 kV PowlVac lineup in a one-high arrangement, with 3,000 A breakers rated 50 kA, for a customer that needs 2,000 A continuous and has 35 kA of fault current available, for an outdoor site. The quote states a basic impulse level of 150 kV. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a 38 kV PowlVac lineup in a one-high arrangement, with 2,000 A breakers rated 40 kA, for a customer that needs 2,000 A continuous and has 35 kA of fault current available, for an outdoor site. The quote states a basic impulse level of 150 kV. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a 38 kV PowlVac lineup in a one-high arrangement, with 2,000 A breakers rated 40 kA, for a customer that needs 2,000 A continuous and has 35 kA of fault current available, for an outdoor site housed in a Power Control Room. The quote states a basic impulse level of 150 kV. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a 5 kV PowlVac lineup in a one-high arrangement, with 4,000 A breakers rated 25 kA, for a customer that needs 4,000 A continuous and has 40 kA of fault current available. The quote states a basic impulse level of 95 kV. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a 5 kV PowlVac lineup in a one-high arrangement, with 4,000 A breakers rated 50 kA, for a customer that needs 4,000 A continuous and has 40 kA of fault current available, with cooling fans. The quote states a basic impulse level of 60 kV. It is ready to send.
Verdict: Allowed.
The text of the narrated walkthrough, step by step.