An AI sales agent prepares an order for a TS IT Pro server rack: height, width, depth, side panels, standard or shiploadable model, the weight of the equipment going in, how the rack will be moved and sited, and the cable, airflow and bracket accessories that go with it. Before it goes out, the agent sends it to Predictika, which checks it against a declarative model of the public Rittal documents and returns a verdict and every reason.
This validator models the TS IT Pro rack as described in the public Rittal sell sheet US1015-OS (5/24), the brochure US618-OS2 (7/22) and the TS IT Pro assembly manual (12/9/20), not just the scenarios shown below.
Any TS IT Pro order that touches these rules is in scope — not only the scenarios pictured here. Not covered: prices (Rittal publishes none for this line), airflow or heat load, seismic ratings, other Rittal enclosure families, and racks assembled from several kits.
6 scenarios in 3 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| Accessories that must match the rack (side panels by height and depth, ducts and walls by height, roof managers and brackets by width) | Only with care Each accessory needs its own lookup over the rack options; a part that fits a 42U rack can look fine on a 48U quote. | The accessory is checked against the rack in the same call. |
| A payload limit that changes when the rack is rolled with equipment installed | Only with workarounds The limit depends on how the rack is moved, not just on the model, so it usually needs custom logic beside the product rules. | The weight is compared with the static limit and, if rolled, the casters limit on every call. |
| A neighbor rack that must match in height and depth, and cannot be moved once bayed | Only with care The neighbor is not part of the product being quoted, so a rules-based CPQ often has nowhere to hold it. | The neighbor is a plain input and is compared with the rack in the same request. |
| Every problem returned in one answer | Only with workarounds Rules tend to fire as the order is saved or a step is completed, so a rep often fixes one error and meets the next. | All findings come back together, whatever order the choices arrived in. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | That height, width, depth, side panel and shiploadable combination is not in the TS IT Pro range (24U only 600 x 1070; 53U only with side panels; shiploadable only 42U or 48U with side panels). |
| 2 | The Rittal brochure says the 53U rack is available build to order; a person should confirm availability and lead time. |
| 3 | Shipping the rack preloaded with equipment needs the shiploadable TS IT Pro. |
| 4 | The equipment weighs 3,800 lb; the static payload of this rack is 3,750 lb. |
| 5 | The equipment weighs 3,200 lb; the static payload of this rack is 3,000 lb. |
| 6 | The rack is rolled with its equipment installed, but the payload on the casters is 2,250 lb and the equipment weighs 2,600 lb. |
| 7 | The sell sheet gives no payload on casters for the 24U rack but the assembly manual gives 2,250 lb; a person should confirm it with Rittal before the loaded rack is rolled. |
| 8 | The TS IT Pro can be bayed only to a TS IT Pro of identical height and depth; the neighbor is 48 U and 1070 mm deep. |
| 9 | The TS IT Pro can be bayed only to a TS IT Pro of identical height and depth; the neighbor is 42 U and 1200 mm deep. |
| 10 | Bayed racks are for static siting only; transporting bayed enclosures is not permitted. |
| 11 | With telescopic slides the rack must be secured to the floor or bayed to another TS IT Pro before devices are extended. |
| 12 | The L and R side panel set must match the rack height and depth. |
| 13 | The vertical cable duct is for 750 mm wide racks and must match the rack height. |
| 14 | The cable management wall must match the rack height. |
| 15 | The cable management fingers must match the rack height (42U, or 48U and 53U). |
| 16 | The roof mount cable manager must match the rack width. |
| 17 | The anti-tip bracket and bolt-down bracket kit must match the rack width. |
| 18 | The PDU mount brackets are for 750 mm wide racks only. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Please quote a TS IT Pro 42U rack, 750 mm wide and 1200 mm deep, with side panels, standard model, for 3,900 lb of equipment. The rack is fitted with telescopic slides, rolled on its casters with the equipment installed. With it: vertical cable duct 239 (42U), anti-tip bracket 292 (750 mm). It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a TS IT Pro 42U rack, 750 mm wide and 1200 mm deep, with side panels, standard model, for 3,600 lb of equipment. The rack is fitted with telescopic slides, bolted to the floor. With it: vertical cable duct 239 (42U), anti-tip bracket 292 (750 mm). It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a TS IT Pro 48U rack, 750 mm wide and 1200 mm deep, with side panels, standard model, for 3,400 lb of equipment. The rack is shipped preloaded. With it: vertical cable duct 240 (48U), cable management wall 296 (48U), cable management fingers 273 (48U and 53U), roof mount cable manager 271 (750 mm), bolt-down bracket kit 294 (750 mm), PDU mount brackets 276. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a TS IT Pro 48U rack, 750 mm wide and 1200 mm deep, with side panels, shiploadable model, for 3,400 lb of equipment. The rack is shipped preloaded. With it: vertical cable duct 240 (48U), cable management wall 296 (48U), cable management fingers 273 (48U and 53U), roof mount cable manager 271 (750 mm), bolt-down bracket kit 294 (750 mm), PDU mount brackets 276. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a TS IT Pro 42U rack, 600 mm wide and 1070 mm deep, with side panels, standard model, for 2,200 lb of equipment. The rack is bayed to a 48U rack 1070 mm deep. With it: roof mount cable manager 270 (600 mm), bolt-down bracket kit 293 (600 mm), foam baffle 261 (42U, 600 mm). It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a TS IT Pro 48U rack, 600 mm wide and 1070 mm deep, without side panels, standard model, for 2,200 lb of equipment. The rack is bayed to a 48U rack 1070 mm deep. With it: roof mount cable manager 270 (600 mm), bolt-down bracket kit 293 (600 mm), foam baffle 262 (48U, 600 mm). It is ready to send.
Verdict: Allowed.
The text of the narrated walkthrough, step by step.