Predictika · Power transformers
An AI sales agent prepares a cast resin transformer for a customer: the rated power and insulation level, the enclosure and protection class, the cooling, the loss and sound figures it quotes, and the site it will stand in. Before it goes out, the agent sends it to Predictika, which checks it against a declarative model of the manufacturer's published planning guide and returns a verdict, every reason and the figures it looked up.
This validator models quotes for SGB-SMIT cast resin transformers as described in the public SGB-SMIT planning guide for cast resin transformers, not just the scenarios shown below.
Any cast resin transformer quote that touches these rules is in scope — not only the scenarios pictured here. Not covered: prices (SGB-SMIT publishes none, so this validator produces no price build-up), liquid-immersed and other transformer types, reduced-loss and low-noise designs, dimensions and weights (the guide gives them as guide values only), and the other planning-guide topics such as lifting and transport. Assumptions: the guide's 10 kV and 20 kV voltage series for standard enclosures are read as the 12 kV and 24 kV insulation levels, the 3160 kVA table row is left out because it lists no losses, and the combination of fan uplift with ambient derating is sent to a person because the guide does not state it.
8 scenarios in 4 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| Enclosure size that depends on rating and voltage series | Only with care Six standard enclosure sizes each take a different maximum rating at 10 kV and 20 kV, so a table has to be loaded and kept in step with the guide, and a too-small enclosure shows up only at engineering. | The enclosure limit is looked up on every call and compared with the rated power. |
| Stated losses and sound power must match the selection table | Only with workarounds Each rating has its own losses and sound level; a rep who reuses the figures of a neighboring rating quotes the wrong ones, and a rule has to compare each figure with the table. | The table figures are looked up on every call and compared with each figure on the quote. |
| Outdoor use needs an enclosure and a protection class | Only with care The rule combines the installation site, the enclosure type and its protection class, and is easy to miss when a rep changes only one of them. | The site, enclosure and protection class are checked together on every call. |
| Load capacity that depends on cooling and ambient temperature | Only with workarounds The capacity is a percentage that depends on the annual average ambient temperature and on fans; it usually lives in an engineering spreadsheet beside the quote. | The capacity is looked up and compared with the load on every call, and shown with the reason. |
| Special systems with their own limits, and gray zones | Only with care The Safe System and the Jet System have their own power ranges, and site classes above the standard need a person, which tends to become a custom approval flow. | Block, needs-approval and allow are separate outcomes, returned with the reasons. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | The planning guide lists no selection table row for 450 kVA at this voltage; losses and dimensions are specific to the order, so a person should confirm the design with SGB-SMIT. |
| 2 | The planning guide covers rated powers from 50 kVA to 25 MVA; the quote has 40 kVA. |
| 3 | Powers above 25 MVA are possible on request only; the quote has 30000 kVA. |
| 4 | The voltage is inside the 1.1 to 40.5 kV range of the guide, but the guide lists selection tables for 12 kV and 24 kV only; a person should confirm the design with SGB-SMIT. |
| 5 | The planning guide covers a maximum operating voltage Um of 1.1 to 40.5 kV; the quote is above that range. |
| 6 | The Safe System is delivered in the power range up to 10 MVA; the quote has 12000 kVA. |
| 7 | The Jet System is delivered in the power range from 1.6 MVA to 4 MVA; the quote has 1000 kVA. |
| 8 | The Safe System and the Jet System are delivered up to a maximum operating voltage Um of 40.5 kV. |
| 9 | The chosen standard enclosure size takes transformers up to 250 kVA at this voltage series; the quote has 1000 kVA, so a larger standard enclosure or a project enclosure is needed. |
| 10 | The chosen standard enclosure size takes transformers up to 630 kVA at this voltage series; the quote has 1000 kVA, so a larger standard enclosure or a project enclosure is needed. |
| 11 | The quote asks for protection class IP34; standard enclosures are offered in IP21, IP23, IP31 and IP33 and project enclosures from IP21 to IP54. |
| 12 | The quote asks for protection class IP55; standard enclosures are offered in IP21, IP23, IP31 and IP33 and project enclosures from IP21 to IP54. |
| 13 | An enclosure is mandatory for outdoor installation, with a minimum protection class of IP23; the quote has none or a lower class. |
| 14 | Air/water cooling (AFWF) is offered with project enclosures; the quote has a different enclosure choice. |
| 15 | A free-standing cast resin transformer is fitted with 2 to 6 fans; the quote has 1. |
| 16 | The continuous load of 1500 kVA is above 140 percent of the rated power of 1000 kVA, the capacity at this cooling and annual average ambient temperature. |
| 17 | The lowest site temperature is 30 degrees below zero, but the climate class on the quote is rated for operation down to 25 degrees below zero. |
| 18 | Configurations up to climate class C2 and environmental class E2 are standard; the higher class on the quote must be requested from SGB-SMIT. |
| 19 | The lowest site temperature is 10 degrees below zero, but the climate class on the quote is rated for operation down to 5 degrees below zero. |
| 20 | The continuous load of 1100 kVA is above 100 percent of the rated power of 1000 kVA, the capacity at this cooling and annual average ambient temperature. |
| 21 | The continuous load of 1130 kVA is above 112 percent of the rated power of 1000 kVA, the capacity at this cooling and annual average ambient temperature. |
| 22 | The continuous load of 940 kVA is above 93 percent of the rated power of 1000 kVA, the capacity at this cooling and annual average ambient temperature. |
| 23 | The guide gives the 40 percent fan uplift and the ambient load capacity separately and does not say how they combine at an annual average ambient of 30 C; a person should confirm. |
| 24 | The guide lists load capacity only for annual average ambient temperatures of -20, -10, 0, 10, 20 and 30 C; the load was not checked at this ambient. |
| 25 | The installation altitude of 1500 m is above 1000 m; the guide asks for it to be communicated so the design can take it into account. |
| 26 | Ships, earthquake zones, wind turbines and EX areas are extreme installation conditions that must be communicated to SGB-SMIT for correct planning. |
| 27 | The guide offers 16 2/3, 50 and 60 Hz; other frequencies are possible on request. |
| 28 | The quote states a no-load loss of 1300 W, but the selection table lists 1550 W for this rating. |
| 29 | The quote states a load loss at 120 C of 9001 W, but the selection table lists 9000 W for this rating. |
| 30 | The quote states a sound power level of 62 dB(A), but the selection table lists 65 dB(A) for this rating. |
| 31 | The quote states a short-circuit voltage of 6 percent, but the selection table lists 4 percent for this rating and voltage. |
| 32 | The quote states a short-circuit voltage of 4 percent, but the selection table lists 6 percent for this rating and voltage. |
| 33 | The chosen standard enclosure size takes transformers up to 315 kVA at this voltage series; the quote has 3150 kVA, so a larger standard enclosure or a project enclosure is needed. |
| 34 | The continuous load of 4500 kVA is above 100 percent of the rated power of 3150 kVA, the capacity at this cooling and annual average ambient temperature. |
| 35 | The quote states a no-load loss of 1550 W, but the selection table lists 3800 W for this rating. |
| 36 | The quote states a load loss at 120 C of 9000 W, but the selection table lists 22000 W for this rating. |
| 37 | The quote states a sound power level of 65 dB(A), but the selection table lists 74 dB(A) for this rating. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Please quote a cast resin transformer, 1250 kVA at 24 kV insulation level, for indoor use, with no enclosure and natural air cooling. The quote states a no-load loss of 1550 W, a load loss of 9000 W, a short-circuit voltage of 6 percent and a sound power level of 67 dB(A). The continuous load is 1000 kVA. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a cast resin transformer, 1250 kVA at 24 kV insulation level, for indoor use, with no enclosure and natural air cooling. The quote states a no-load loss of 1800 W, a load loss of 11000 W, a short-circuit voltage of 6 percent and a sound power level of 67 dB(A). The continuous load is 1000 kVA. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a cast resin transformer, 1600 kVA at 12 kV insulation level, for indoor use, with a standard enclosure of size 3 at protection class IP23 and natural air cooling. The quote states a no-load loss of 2200 W, a load loss of 13000 W, a short-circuit voltage of 6 percent and a sound power level of 68 dB(A). The continuous load is 1280 kVA. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a cast resin transformer, 1600 kVA at 12 kV insulation level, for indoor use, with a standard enclosure of size 4 at protection class IP23 and natural air cooling. The quote states a no-load loss of 2200 W, a load loss of 13000 W, a short-circuit voltage of 6 percent and a sound power level of 68 dB(A). The continuous load is 1280 kVA. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a cast resin transformer, 630 kVA at 12 kV insulation level, for outdoor use, with no enclosure and natural air cooling. The quote states a no-load loss of 1100 W, a load loss of 7600 W, a short-circuit voltage of 4 percent and a sound power level of 62 dB(A). The continuous load is 700 kVA. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a cast resin transformer, 630 kVA at 12 kV insulation level, for outdoor use, with a project enclosure at protection class IP54 and fan cooling with 4 fans. The quote states a no-load loss of 1100 W, a load loss of 7600 W, a short-circuit voltage of 4 percent and a sound power level of 62 dB(A). The continuous load is 700 kVA. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a Jet System cast resin transformer, 1000 kVA at 12 kV insulation level, for indoor use with a continuous load of 800 kVA. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a Jet System cast resin transformer, 2000 kVA at 12 kV insulation level, for indoor use with a continuous load of 1600 kVA. It is ready to send.
Verdict: Allowed.
The text of the narrated walkthrough, step by step.