Predictika · Fire dampers for air duct systems
An AI sales agent prepares an order for round fire dampers from a public product data sheet, with a casing, a release device, accessories, an installation method and operating conditions. Before it goes out, the agent sends it to Predictika, which checks it against a declarative model of the data sheet and returns a verdict, every reason and the figures it computed.
This validator models orders for the FKR-EU fire damper, not just the scenarios shown below.
Any FKR-EU order that touches these rules is in scope — not only the scenarios pictured here. Not covered: prices (TROX publishes no list prices, so this validator produces no price build-up or line-item quote), other TROX damper types, fire resistance classes for each wall construction, minimum distances and the full list of permitted wall and ceiling types. Assumptions: the data sheet was read through summarising fetches, so only rules that matched across reads are used; the approval for dry mortarless installation in solid masonry and for a 95 °C release with an actuator are this model's cautious readings of what the data sheet lists, not stated TROX prohibitions.
7 scenarios in 3 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| An accessory that only one casing accepts: the TQ kit on spigot dampers | Only with care The kit depends on the casing on another field, so it needs a cross-field rule, and every accessory adds another. | The casing and the accessory travel in one request and the combination is checked on every call. |
| Limits that depend on the release device: velocity 8, 12 or 10 m/s | Only with care Each construction has its own limit, so each needs its own comparison that must be kept in step with the data sheet. | The release device and the velocity are in one request and the limit is looked up and checked every time. |
| A network module that needs one actuator make and voltage | Only with workarounds The condition spans three fields (release, make, voltage), so it needs a compound rule that interacts with the others. | All three fields are in the same request and the combination is checked with the rest. |
| A construction that needs both an actuator and a mortar installation (ODA) | Only with workarounds Two dependencies on different fields have to be tied to one option, and a missing match is often caught only at the end. | All items are in one request and every dependency is checked together. |
| Every problem returned in one answer | Only with workarounds Rules tend to fire as the order is saved or a step is completed, so a rep often fixes one error and meets the next. | All findings come back together, whatever order the choices arrived in. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | Nominal size 600 mm is not offered; the data sheet gives 315, 355, 400, 450, 500, 560, 630, 710 and 800 mm. |
| 2 | The quote states a casing length of 550 mm; the data sheet gives 495 mm for the selected casing. |
| 3 | The square installation kit (TQ) is for the spigot design only; it cannot be combined with the flanged (FL) casing. |
| 4 | Dry mortarless installation uses the square installation kit (TQ); the quote has none. |
| 5 | The data sheet lists dry mortarless installation for lightweight metal-stud, timber stud and solid timber constructions; a solid masonry wall is not listed, so a person should confirm it. |
| 6 | The ODA (outdoor air, insulated) construction is available only with a spring return actuator. |
| 7 | The ODA construction is suitable only for mortar-based installation with perimeter mortar infill. |
| 8 | Limit switches (Z00 to Z03) are for fusible link versions; this damper has a spring return actuator. |
| 9 | The TROXNETCOM modules are offered only with the 24 V Belimo spring return actuator. |
| 10 | The 95 C release temperature is for warm air ventilation systems only. |
| 11 | The 95 C release is listed for the fusible link; the spring return actuator releases at 72 C, so a person should confirm this combination. |
| 12 | In areas with potentially explosive atmospheres the damper needs an explosion-proof actuator. |
| 13 | The upstream velocity is 9 m/s; this construction allows at most 8 m/s. |
| 14 | The upstream velocity is 11 m/s; this construction allows at most 10 m/s. |
| 15 | The differential pressure is 2,100 Pa; the data sheet gives up to 2,000 Pa. |
| 16 | The air temperature is 55 C; the data sheet gives -20 to 50 C. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Please quote 12 FKR-EU fire dampers of nominal size 630 mm with a flanged casing, with a fusible link, a 72 C release, with the TQ installation kit, for dry mortarless installation in a metal-stud partition, in a standard ventilation system, at 6 m/s upstream velocity and 900 Pa differential pressure. The quote states a casing length of 495 mm. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote 12 FKR-EU fire dampers of nominal size 630 mm with a spigot casing, with a fusible link, a 72 C release, with the TQ installation kit, for dry mortarless installation in a metal-stud partition, in a standard ventilation system, at 6 m/s upstream velocity and 900 Pa differential pressure. The quote states a casing length of 550 mm. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote 8 FKR-EU fire dampers of nominal size 500 mm with a spigot casing, with a spring return actuator (Siemens, 230 V), a 72 C release, with limit switches and a TROXNETCOM module, for mortar-based installation in a solid masonry wall, in a standard ventilation system, at 13 m/s upstream velocity and 700 Pa differential pressure. The quote states a casing length of 550 mm. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote 8 FKR-EU fire dampers of nominal size 500 mm with a spigot casing, with a spring return actuator (Siemens, 230 V), a 72 C release, with a TROXNETCOM module, for mortar-based installation in a solid masonry wall, in a standard ventilation system, at 11 m/s upstream velocity and 700 Pa differential pressure. The quote states a casing length of 550 mm. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote 8 FKR-EU fire dampers of nominal size 500 mm with a spigot casing, with a spring return actuator (Belimo, 24 V), a 72 C release, with a TROXNETCOM module, for mortar-based installation in a solid masonry wall, in a standard ventilation system, at 11 m/s upstream velocity and 700 Pa differential pressure. The quote states a casing length of 550 mm. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote 10 FKR-EU fire dampers of nominal size 400 mm with a spigot casing, with a fusible link, a 95 C release, with the ODA construction, for mortar-based installation in a solid masonry wall, in a standard ventilation system, at 7 m/s upstream velocity and 600 Pa differential pressure. The quote states a casing length of 550 mm. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote 10 FKR-EU fire dampers of nominal size 400 mm with a spigot casing, with a spring return actuator (Belimo, 24 V), a 72 C release, with the ODA construction, for mortar-based installation in a solid masonry wall, in a warm air ventilation system, at 7 m/s upstream velocity and 600 Pa differential pressure. The quote states a casing length of 550 mm. It is ready to send.
Verdict: Allowed.
The text of the narrated walkthrough, step by step.