Predictika · Self-regulating heat tracing
An AI sales agent specifies a self-regulating heat trace circuit for a pipe from public product documents, choosing the cable rating, supply voltage and breaker for the circuit. Before it goes out, the agent sends it to Predictika, which checks it against a declarative model of those documents and returns a verdict, every reason and the figures it computed.
This validator models circuits for the Thermon FLX self-regulating heat trace family (3-FLX, 5-FLX, 8-FLX and 10-FLX at 120 or 240 Vac), not just the scenarios shown below.
Any circuit for this cable family that touches these rules is in scope — not only the scenarios pictured here. Not covered: prices (Thermon publishes none for these products, so this validator produces no price build-up or line-item quote), nonmetallic pipe design (Chart 2.2), the 230 volt tables, other Thermon cables and products, heat-loss design beyond the selection chart, and local code requirements.
7 scenarios in 3 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| A maximum circuit length that depends on cable, voltage, breaker and start-up temperature | Only with care The table has a different value for each combination, so it takes a lookup per combination and a comparison with the circuit length including allowances. | Cable, voltage, breaker, start-up temperature, pipe run and splice counts travel in one request; the maximum is looked up and compared on every call. |
| A cable rating that depends on pipe size, insulation and minimum ambient temperature | Only with workarounds The selection chart changes by insulation thickness and pipe size row, with some cells saying to contact the manufacturer, so the rules multiply and are easy to miss when a row is added. | The chart is part of the model; the chart rating is compared with the cable on every call, and the contact-the-manufacturer cells go to a person. |
| A stated maximum length that disagrees with the table | Only with workarounds The figure the agent states is free text or a separate field, so it takes an extra rule that compares it with the table value. | The stated figure is part of the request and is compared with the table figure on every call. |
| Every problem returned in one answer | Only with workarounds Rules tend to fire as the order is saved or a step is completed, so a rep often fixes one error and meets the next. | All findings come back together, whatever order the choices arrived in. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | The order uses 8-FLX; Design Selection Chart 2.1 calls for 10-FLX for this pipe size, insulation thickness and minimum ambient temperature. |
| 2 | The order uses 3-FLX; Design Selection Chart 2.1 calls for 5-FLX for this pipe size, insulation thickness and minimum ambient temperature. |
| 3 | The order uses 5-FLX; Design Selection Chart 2.1 calls for 8-FLX for this pipe size, insulation thickness and minimum ambient temperature. |
| 4 | Design Selection Chart 2.1 says to contact Thermon for this pipe size, insulation thickness and minimum ambient temperature, so a person should confirm the cable rating with Thermon. |
| 5 | The order uses 5-FLX; Design Selection Chart 2.1 calls for 10-FLX for this pipe size, insulation thickness and minimum ambient temperature. |
| 6 | Design Selection Chart 2.1 has no entry for this pipe size with this insulation thickness, so a person should confirm the cable rating with Thermon. |
| 7 | The circuit needs 108.1 m of cable including allowances; the maximum circuit length for this cable, voltage, breaker size and start-up temperature is 108.0 m. |
| 8 | The circuit needs 73.1 m of cable including allowances; the maximum circuit length for this cable, voltage, breaker size and start-up temperature is 73.0 m. |
| 9 | The circuit needs 88.1 m of cable including allowances; the maximum circuit length for this cable, voltage, breaker size and start-up temperature is 88.0 m. |
| 10 | The circuit needs 76.3 m of cable including allowances; the maximum circuit length for this cable, voltage, breaker size and start-up temperature is 76.0 m. |
| 11 | The circuit needs 117.3 m of cable including allowances; the maximum circuit length for this cable, voltage, breaker size and start-up temperature is 117.0 m. |
| 12 | The circuit needs 73.4 m of cable including allowances; the maximum circuit length for this cable, voltage, breaker size and start-up temperature is 73.0 m. |
| 13 | The circuit needs 214.5 m of cable including allowances; the maximum circuit length for this cable, voltage, breaker size and start-up temperature is 214.0 m. |
| 14 | The circuit needs 27.3 m of cable including allowances; the maximum circuit length for this cable, voltage, breaker size and start-up temperature is 27.0 m. |
| 15 | The circuit breaker has no 30 mA ground-fault protection; the design guide requires 30 mA ground-fault equipment protection on circuits supplying FLX heat trace. |
| 16 | The order does not include the minimum installation accessories listed in the design guide (a PCA-COM circuit fabrication kit, FT-1L fixing tape and ET-6 end terminations). |
| 17 | The pipe is nonmetallic, so the design guide uses Design Selection Chart 2.2 (output is lower because of the pipe wall) and requires AL-20L aluminum foil tape; this validator does not model that chart, so a person should confirm the cable rating. |
| 18 | The circuit needs 90.3 m of cable including allowances; the maximum circuit length for this cable, voltage, breaker size and start-up temperature is 73.0 m. |
| 19 | The order states a maximum circuit length of 60 m; the Thermon table gives 73.0 m for this cable, voltage, breaker size and start-up temperature. |
| 20 | The order states a maximum circuit length of 88 m; the Thermon table gives 73.0 m for this cable, voltage, breaker size and start-up temperature. |
| 21 | The order uses 3-FLX; Design Selection Chart 2.1 calls for 8-FLX for this pipe size, insulation thickness and minimum ambient temperature. |
| 22 | The circuit needs 150.3 m of cable including allowances; the maximum circuit length for this cable, voltage, breaker size and start-up temperature is 108.0 m. |
| 23 | The order states a maximum circuit length of 300 m; the Thermon table gives 108.0 m for this cable, voltage, breaker size and start-up temperature. |
| 24 | The circuit needs 100.3 m of cable including allowances; the maximum circuit length for this cable, voltage, breaker size and start-up temperature is 48.0 m. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Please quote a 5-FLX heat trace circuit at 120 volt on a 20 amp breaker for a 70 metre run of DN80 metallic pipe with 25 mm insulation, a minimum ambient of minus 29 degrees C and a start-up temperature of minus 20 degrees C, with 30 mA ground-fault protection and including the minimum accessories, and a maximum circuit length of 73 metres. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a 10-FLX heat trace circuit at 240 volt on a 20 amp breaker for a 70 metre run of DN80 metallic pipe with 25 mm insulation, a minimum ambient of minus 29 degrees C and a start-up temperature of minus 20 degrees C, with 30 mA ground-fault protection and including the minimum accessories. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a 10-FLX heat trace circuit at 240 volt on a 30 amp breaker for a 70 metre run of DN80 metallic pipe with 25 mm insulation, a minimum ambient of minus 29 degrees C and a start-up temperature of minus 20 degrees C, with 30 mA ground-fault protection and including the minimum accessories, and a maximum circuit length of 101 metres. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a 8-FLX heat trace circuit at 240 volt on a 30 amp breaker for a 120 metre run of DN100 metallic pipe with 38 mm insulation, a minimum ambient of minus 23 degrees C and a start-up temperature of 10 degrees C, without 30 mA ground-fault protection and without the minimum accessories, and a maximum circuit length of 154 metres. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a 8-FLX heat trace circuit at 240 volt on a 30 amp breaker for a 120 metre run of DN100 metallic pipe with 38 mm insulation, a minimum ambient of minus 23 degrees C and a start-up temperature of 10 degrees C, with 30 mA ground-fault protection and including the minimum accessories, and a maximum circuit length of 154 metres. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a 10-FLX heat trace circuit at 120 volt on a 20 amp breaker for a 40 metre run of DN50 metallic pipe with 25 mm insulation, a minimum ambient of minus 40 degrees C and a start-up temperature of 10 degrees C, with 30 mA ground-fault protection and including the minimum accessories, and a maximum circuit length of 48 metres. It is ready to send.
Verdict: Needs approval.
The agent's request. Please quote a 8-FLX heat trace circuit at 120 volt on a 30 amp breaker for a 40 metre run of DN50 metallic pipe with 50 mm insulation, a minimum ambient of minus 40 degrees C and a start-up temperature of 10 degrees C, with 30 mA ground-fault protection and including the minimum accessories, and a maximum circuit length of 81 metres. It is ready to send.
Verdict: Allowed.
The text of the narrated walkthrough, step by step.