Predictika · Electric shower installation: model, power rating, circuit protection, cable, water supply and site

An AI sales agent's Triton electric shower installation, checked before it goes out

An AI sales agent prepares the specification for installing a Triton electric shower in a customer's bathroom: the model and power rating, the circuit breaker and cable, the fittings on the circuit, and the mains water supply at the site. Before it goes out, the agent sends it to Predictika, which checks it against a declarative model of the rules in Triton's published installation guides and returns a verdict, every reason and the figures it computed.

Scope: Triton electric showers: Amala, Amore, Aspirante, Zante 5, Danzi, T80Z Fast-Fit, T80Z Thermostatic Fast-Fit and T80 Pro-Fit (7.5 to 10.5 kW): power rating, circuit protection, cable, water supply, site and stated figures. See everything this validator covers

This validator models installation specifications for eight Triton electric shower models covered by the installation guides listed below, not just the scenarios shown on this page.

  • Models and ratings — Amala, Amore, Aspirante and Zante 5 (8.5 and 9.5 kW), Danzi (8.5, 9.5 and 10.5 kW), T80Z Fast-Fit and T80 Pro-Fit (7.5, 8.5, 9.5 and 10.5 kW) and T80Z Thermostatic Fast-Fit (8.5, 9.5 and 10.5 kW), with the 230 V figure each rating delivers.
  • Circuit protection and cable — the circuit breaker each rating needs (32, 40 or 45 A), the current each cable size (6, 10 or 16 mm²) carries in an insulated wall, in conduit or trunking and clipped direct, the 30 mA RCD, the independent circuit, the 45 A double pole isolating switch and the 80 A consumer unit main switch.
  • Water supply and site — mains cold water only, the minimum running pressure and flow (100 kPa at 8 litres per minute, and 150 kPa at 11 litres per minute for 10.5 kW), the 1,000 kPa maximum static pressure, the inlet temperature range of each model and the ban on steam rooms.
  • Items for a person — a cable below the recommended 10 mm², no spare fuse way, a rating above 9 kW with the electricity supplier not yet contacted, and water harder than 200 ppm.

Any installation specification for these eight models that touches these rules is in scope — not only the scenarios pictured here. Not covered: prices (Triton's retail prices vary by variant and are not modeled, so this validator produces no price build-up or line-item quote), DuElec, UNIQ, ENlight and ENVi kits and other Triton products, power showers, accessories, finishes, and installation work beyond what the guides state.

The AI sales agentBuilds the installation specification from the conversation and says it is ready.
Predictika validatorChecks every rule at once and returns the verdict, each finding, and the computed figures.

7 scenarios in 3 groups · each group runs from the agent’s first attempt to the outcome · click one to switch

What the agent proposes

The AI sales agent says

Illustrative agent statement. The validator receives the structured request below.

Proposing agent: AI sales agent (scripted)

Before sending, the agent must call Recorded run

Predictika validator


      
Waiting for the call.

Where rules-based CPQ gets it wrong

Click to expand

Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.

What the validator caughtTypical rules-based CPQPredictika
Circuit breaker that depends on the ratingOnly with care
The breaker size is a lookup on the rating, and some ratings allow a range, so a rule per rating has to be written and kept in step with the guide.
The breaker is checked against the minimum and maximum for the chosen rating on every call.
Cable that must carry the breaker currentOnly with workarounds
The current a cable carries depends on its size and how it is installed, so the check needs a table across two choices, and it is easy to leave out when only the cable size is validated.
Size and installation method are looked up together and compared with the breaker rating.
Ratings that only some models are made inOnly with care
Each model offers a different range of ratings, so every model needs its own rule that a rep can bypass by typing a different rating.
The model's range is looked up and the rating is checked against it.
Water limits that change with the rating and modelOnly with workarounds
Minimum pressure and flow change at 10.5 kW and the inlet temperature range changes by model, so the rules interlock across three choices.
Rating and model set the limits, and the site's pressure, flow and temperature are checked against them together.
Stated figures against the ratingOnly with care
A stated 230 V rating or minimum flow is a free-entry field; a rule can compare it with the rating, but only if someone writes and maintains that lookup.
The stated figures travel with the specification and are compared with the computed ones on every call.
Every problem returned in one answerOnly with workarounds
Rules tend to fire as the quote is saved or a step is completed, so a rep often fixes one error and meets the next.
All findings come back together, whatever order the choices arrived in.

What this validator catches: findings from its test cases

Click to expand

Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.

1The selected model is not made as a 10.5 kW shower; it is offered from 8.5 kW to 9.5 kW.
2The selected model is not made as a 7.5 kW shower; it is offered from 8.5 kW to 10.5 kW.
3The running mains pressure is 149 kPa, below the 150 kPa this rating needs.
4The mains flow is 10 litres per minute, below the 11 litres per minute this rating needs.
5The running mains pressure is 99 kPa, below the 100 kPa this rating needs.
6The mains flow is 7 litres per minute, below the 8 litres per minute this rating needs.
7The static mains pressure is 1,001 kPa, above the 1,000 kPa (10 bar) maximum.
8The inlet water temperature is 4 degrees C, outside the 5 to 28 degrees C this model accepts.
9The inlet water temperature is 26 degrees C, outside the 5 to 25 degrees C this model accepts.
10Electric showers need a mains pressure cold water supply; a tank-fed supply is not suitable.
11The shower is not suitable for mounting in a steam room or steam cubicle.
12The circuit breaker is 32 A, below the 40 A this rating needs.
13The circuit breaker is 50 A, above the 45 A the installation guide gives for this rating.
14The circuit breaker is 45 A, above the 40 A the installation guide gives for this rating.
15The 10 mm² cable carries 43 A when installed this way, less than the 45 A circuit breaker.
16The guide strongly recommends at least 10 mm² cable throughout; this quote uses 6 mm², so an electrician should confirm it.
17The 6 mm² cable carries 38 A when installed this way, less than the 40 A circuit breaker.
18A 30 mA residual current device is required on every electric shower circuit.
19The shower must be on its own independent circuit, not a ring main, spur, socket, lighting or cooker circuit.
20A 45 A double pole isolating switch with a 3 mm contact gap in both poles is required in the circuit.
21The consumer unit main switch is 63 A; the guide requires 80 A or above.
22The consumer unit has no spare fuse way, so a new consumer unit may be needed; an electrician should assess it.
23For a shower rated above 9 kW the guide advises contacting the local electricity supply company; a person should confirm it has been done.
24The water hardness is 201 ppm, above 200 ppm, so a scale inhibitor may be needed; a person should contact the manufacturer.
25The quote states a 230 V rating of 9.6 kW, but this rating delivers 8.7 kW at 230 V.
26The quote states a minimum flow of 8 litres per minute, but this rating needs 11 litres per minute.
27The water hardness is 250 ppm, above 200 ppm, so a scale inhibitor may be needed; a person should contact the manufacturer.

Scenarios and results

Click to expand

The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.

1. Rating and cable: A 10.5 kW Amala on a 10 mm² cable in an insulated wall

The agent's request. Please specify the installation of one Triton Amala electric shower rated 10.5 kW at 240 V for a customer of Kestrel Plumbing and Heating. It is on a 45 A circuit breaker with 10 mm² cable run in an insulated wall, with a 30 mA RCD, its own independent circuit, a 45 A double pole isolating switch and a spare fuse way, on a consumer unit with a 100 A main switch; the local electricity supply company has been contacted. The site has a mains cold water supply at 200 kPa running pressure, 12 litres per minute, 500 kPa static pressure, 12 degrees C inlet temperature and 100 ppm water hardness; the shower is for a bathroom, not a steam room. The specification states a 230 V rating of 9.6 kW and a minimum mains flow of 8 litres per minute. It is ready to send.

Verdict: Blocked.

  • Power rating not offered for this model. The selected model is not made as a 10.5 kW shower; it is offered from 8.5 kW to 9.5 kW.
  • Cable cannot carry the breaker rating. The 10 mm² cable carries 43 A when installed this way, less than the 45 A circuit breaker.
  • Stated minimum flow does not match. The quote states a minimum flow of 8 litres per minute, but this rating needs 11 litres per minute.

2. Rating and cable: The agent resubmits after fixing the errors

The agent's request. Please specify the installation of one Triton Danzi electric shower rated 10.5 kW at 240 V for a customer of Kestrel Plumbing and Heating. It is on a 45 A circuit breaker with 16 mm² cable run in an insulated wall, with a 30 mA RCD, its own independent circuit, a 45 A double pole isolating switch and a spare fuse way, on a consumer unit with a 100 A main switch; the local electricity supply company has been contacted. The site has a mains cold water supply at 200 kPa running pressure, 12 litres per minute, 500 kPa static pressure, 12 degrees C inlet temperature and 100 ppm water hardness; the shower is for a bathroom, not a steam room. The specification states a 230 V rating of 9.6 kW and a minimum mains flow of 11 litres per minute. It is ready to send.

Verdict: Allowed.

  • Installation summary. Rated 10.5 kW (about 9.6 kW at 230 V), needing a circuit breaker of 45 A to 45 A, at least 150 kPa and 11 litres per minute from the mains; this cable installation carries 57 A.

3. Circuit protection and fittings: A 9.5 kW T80Z Fast-Fit on a 32 A breaker with no RCD and no isolating switch

The agent's request. Please specify the installation of one Triton T80Z Fast-Fit electric shower rated 9.5 kW at 240 V for a customer of Kestrel Plumbing and Heating. It is on a 32 A circuit breaker with 6 mm² cable run clipped direct, with its own independent circuit and a spare fuse way, on a consumer unit with a 100 A main switch; the local electricity supply company has been contacted. The site has a mains cold water supply at 200 kPa running pressure, 12 litres per minute, 500 kPa static pressure, 12 degrees C inlet temperature and 100 ppm water hardness; the shower is for a bathroom, not a steam room. The specification states a 230 V rating of 8.7 kW and a minimum mains flow of 11 litres per minute. It is ready to send.

Verdict: Blocked.

  • Circuit breaker too small. The circuit breaker is 32 A, below the 40 A this rating needs.
  • No 30 mA RCD. A 30 mA residual current device is required on every electric shower circuit.
  • No 45 A double pole isolating switch. A 45 A double pole isolating switch with a 3 mm contact gap in both poles is required in the circuit.
  • Stated minimum flow does not match. The quote states a minimum flow of 11 litres per minute, but this rating needs 8 litres per minute.
  • Cable below the recommended 10 mm2. The guide strongly recommends at least 10 mm² cable throughout; this quote uses 6 mm², so an electrician should confirm it.

4. Circuit protection and fittings: The agent resubmits after fixing the errors

The agent's request. Please specify the installation of one Triton T80Z Fast-Fit electric shower rated 9.5 kW at 240 V for a customer of Kestrel Plumbing and Heating. It is on a 40 A circuit breaker with 6 mm² cable run clipped direct, with a 30 mA RCD, its own independent circuit, a 45 A double pole isolating switch and a spare fuse way, on a consumer unit with a 100 A main switch. The site has a mains cold water supply at 200 kPa running pressure, 12 litres per minute, 500 kPa static pressure, 12 degrees C inlet temperature and 100 ppm water hardness; the shower is for a bathroom, not a steam room. The specification states a 230 V rating of 8.7 kW and a minimum mains flow of 8 litres per minute. It is ready to send.

Verdict: Needs approval.

  • Cable below the recommended 10 mm2. The guide strongly recommends at least 10 mm² cable throughout; this quote uses 6 mm², so an electrician should confirm it.
  • Electricity supplier to be contacted. For a shower rated above 9 kW the guide advises contacting the local electricity supply company; a person should confirm it has been done.
  • Installation summary. Rated 9.5 kW (about 8.7 kW at 230 V), needing a circuit breaker of 40 A to 45 A, at least 100 kPa and 8 litres per minute from the mains; this cable installation carries 46 A.

5. Circuit protection and fittings: The agent resubmits after fixing the errors

The agent's request. Please specify the installation of one Triton T80Z Fast-Fit electric shower rated 9.5 kW at 240 V for a customer of Kestrel Plumbing and Heating. It is on a 40 A circuit breaker with 10 mm² cable run in conduit or trunking, with a 30 mA RCD, its own independent circuit, a 45 A double pole isolating switch and a spare fuse way, on a consumer unit with a 100 A main switch; the local electricity supply company has been contacted. The site has a mains cold water supply at 200 kPa running pressure, 12 litres per minute, 500 kPa static pressure, 12 degrees C inlet temperature and 100 ppm water hardness; the shower is for a bathroom, not a steam room. The specification states a 230 V rating of 8.7 kW and a minimum mains flow of 8 litres per minute. It is ready to send.

Verdict: Allowed.

  • Installation summary. Rated 9.5 kW (about 8.7 kW at 230 V), needing a circuit breaker of 40 A to 45 A, at least 100 kPa and 8 litres per minute from the mains; this cable installation carries 52 A.

6. Water inlet temperature: A 10.5 kW T80Z Thermostatic Fast-Fit at a 27 degree inlet on a 50 A breaker

The agent's request. Please specify the installation of one Triton T80Z Thermostatic Fast-Fit electric shower rated 10.5 kW at 240 V for a customer of Kestrel Plumbing and Heating. It is on a 50 A circuit breaker with 16 mm² cable run in conduit or trunking, with a 30 mA RCD, its own independent circuit, a 45 A double pole isolating switch and a spare fuse way, on a consumer unit with a 100 A main switch; the local electricity supply company has been contacted. The site has a mains cold water supply at 200 kPa running pressure, 12 litres per minute, 500 kPa static pressure, 27 degrees C inlet temperature and 100 ppm water hardness; the shower is for a bathroom, not a steam room. The specification states a 230 V rating of 9.0 kW and a minimum mains flow of 11 litres per minute. It is ready to send.

Verdict: Blocked.

  • Inlet water temperature out of range. The inlet water temperature is 27 degrees C, outside the 5 to 25 degrees C this model accepts.
  • Circuit breaker too large. The circuit breaker is 50 A, above the 45 A the installation guide gives for this rating.
  • Stated 230 V rating does not match. The quote states a 230 V rating of 9.0 kW, but this rating delivers 9.6 kW at 230 V.

7. Water inlet temperature: The agent resubmits after fixing the errors

The agent's request. Please specify the installation of one Triton T80Z Fast-Fit electric shower rated 10.5 kW at 240 V for a customer of Kestrel Plumbing and Heating. It is on a 45 A circuit breaker with 16 mm² cable run in conduit or trunking, with a 30 mA RCD, its own independent circuit, a 45 A double pole isolating switch and a spare fuse way, on a consumer unit with a 100 A main switch; the local electricity supply company has been contacted. The site has a mains cold water supply at 200 kPa running pressure, 12 litres per minute, 500 kPa static pressure, 27 degrees C inlet temperature and 100 ppm water hardness; the shower is for a bathroom, not a steam room. The specification states a 230 V rating of 9.6 kW and a minimum mains flow of 11 litres per minute. It is ready to send.

Verdict: Allowed.

  • Installation summary. Rated 10.5 kW (about 9.6 kW at 230 V), needing a circuit breaker of 45 A to 45 A, at least 150 kPa and 11 litres per minute from the mains; this cable installation carries 69 A.

Narration transcript

Click to expand

The text of the narrated walkthrough, step by step.

  1. Welcome to a demo of Predictika's Validator. An AI sales agent prepares the specification for installing a Triton electric shower in a customer's bathroom: the model and power rating, the circuit breaker and cable, the fittings on the circuit, and more. Before it goes out, the agent sends it to Predictika, which checks it against a declarative model of the rules in Triton's published installation guides and returns a verdict, every reason and the figures it computed.
  2. I will start with the first request by the agent.
  3. The agent says. Please specify the installation of one Triton T80Z Fast-Fit electric shower rated 9.5 kW at 240 V for a customer of Kestrel Plumbing and Heating. It is on a 32 A circuit breaker with 6 mm² cable run clipped direct, with its own independent circuit and a spare fuse way. The rest of the request is on screen.
  4. Before it goes out, the agent calls the validator.
  5. Blocked, with four findings and one approval, all in one answer. The circuit breaker is 32 A, below the 40 A this rating needs. A 30 mA residual current device is required on every electric shower circuit. A 45 A double pole isolating switch with a 3 mm contact gap in both poles is required in the circuit. The other one is on screen.
  6. The validator returned four blocking findings and one approval in one answer. A check that reads one field at a time would pass most of this; it shows only when the choices in the quote are checked against each other.
  7. What this shows: for circuit breaker that depends on the rating, a rules-based CPQ is error-prone for this.
  8. Now the agent resubmits.
  9. The corrected request. It changes the circuit breaker to 40 A, the 30 mA RCD to yes, the 45 A double pole isolating switch to yes, the electricity supply company contacted to no and the stated minimum flow to 8 litres per minute.
  10. It calls the validator again.
  11. Not blocked, but held for a person.
  12. The four blocking findings are cleared; two approvals remain for a person: cable below the recommended 10 mm2 and electricity supplier to be contacted.
  13. The agent resubmits once more.
  14. The revised request. It changes the cable size to 10, the cable installed to conduit or trunking and the electricity supply company contacted to yes.
  15. It calls the validator once more.
  16. This time the validator clears it.
  17. Both earlier findings are cleared, and the validator's figure matches the quote.
  18. Five problems caught in one call, fixed in two passes, and a clean quote. That is the value of Predictika's validator: catching mistakes before they reach the customer. Now you can try the other scenarios yourself.