Predictika · Ducted air conditioners
An AI sales agent prepares an order for air-cooled ductable split air conditioners from a public product catalogue: the set model, the number of sets, the indoor and outdoor units, the electrical supply, the breaker, the interlocking cable and the pipe run. Before it goes out, the agent sends it to Predictika, which checks it against a declarative model of the catalogue and returns a verdict, every reason and the figures it computed.
This validator models orders for the air-cooled ductable split air conditioner sets in the public Voltas Package and Ducted AC catalogue, not just the scenarios shown below.
Any order for these air-cooled ductable split sets that touches these rules is in scope — not only the scenarios pictured here. Not covered: prices (the catalogue lists none, so this validator produces no price build-up or line-item quote), water-cooled ductable sets, packaged units, the 10 TR set with a single outdoor unit, VRF and other Voltas product families, duct design, cable and pipe sizing, and electrical or local-code compliance. Assumptions: a breaker rating at or above the catalogue rating is accepted, and the pipe run is entered as an equivalent length in whole metres.
8 scenarios in 3 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| A set model that must belong to the refrigerant series ordered | Only with care Model numbers differ by series and by refrigerant, so a rule per series has to be kept in step with the catalogue. | The set model carries its series, which is compared with the series ordered on every call. |
| Indoor and outdoor units, and the outdoor unit count, that depend on the set model | Only with care Each set implies a fixed pair of units and a count; a lookup per set works, but the stated units are free fields that need their own comparison rules. | Units and count are part of the request and compared with the set on every call. |
| A stated total capacity that disagrees with the sets ordered | Only with workarounds The figure the agent states is a free field, so it takes an extra rule that multiplies the set capacity by the quantity and compares. | The stated figure is part of the request and is compared with the computed capacity on every call. |
| A pipe run that goes to a person above a length | Only with workarounds A threshold that turns a quote from allowed to needing approval, next to blocking rules, takes separate routing logic. | Blocks and approvals come from the same model; a long pipe run adds an approval without hiding any block. |
| Every problem returned in one answer | Only with workarounds Rules tend to fire as the order is saved or a step is completed, so a rep often fixes one error and meets the next. | All findings come back together, whatever order the choices arrived in. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | The set model is not listed in the selected refrigerant series of the catalogue (R22, R407C and R410A sets have different model numbers). |
| 2 | The order has 0 sets; at least 1 is needed. |
| 3 | The indoor unit stated is not the indoor unit the catalogue lists for this set model. |
| 4 | The outdoor unit stated is not the outdoor unit the catalogue lists for this set model. |
| 5 | The order lists 1 outdoor unit per set; the catalogue lists 2 for this set model. |
| 6 | The order lists 2 outdoor units per set; the catalogue lists 1 for this set model. |
| 7 | The outdoor units are listed for a 3-phase, 415 V, 50 Hz supply, and a different supply is selected. |
| 8 | The indoor units are listed for a single-phase, 230 V, 50 Hz supply, and a different supply is selected. |
| 9 | The order has a 62 A breaker; the catalogue lists 63 A for this set model. |
| 10 | The order has no interlocking cable between indoor and outdoor unit; the catalogue notes that one more interlocking cable of 3C x 1.5 sq mm is required. |
| 11 | The order states a total capacity of 23 TR; the sets ordered give 22 TR. |
| 12 | The order states a total capacity of 34 TR; the sets ordered give 51 TR. |
| 13 | The pipe run is 8 m between outdoor and indoor unit; the catalogue piping sizes are recommended for 7.5 m equivalent length and Voltas asks buyers to contact a representative for longer runs, and the refrigerant charge then needs topping up at site. |
| 14 | The pipe run is 12 m between outdoor and indoor unit; the catalogue piping sizes are recommended for 7.5 m equivalent length and Voltas asks buyers to contact a representative for longer runs, and the refrigerant charge then needs topping up at site. |
| 15 | The order has a 100 A breaker; the catalogue lists 125 A for this set model. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Please quote 6 sets of Voltas air-cooled ductable split model ACADS17023 under the R22 series, each with indoor unit ACDEU170C2ZGIMR410 and 2 outdoor units ACDCUA08513, on a single-phase, 230 V outdoor supply and a single-phase, 230 V indoor supply, with a 100 A breaker, and a pipe run of 5 m between outdoor and indoor unit. The order states a total capacity of 102 TR. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote 6 sets of Voltas air-cooled ductable split model ACADS17023 under the R410A series, each with indoor unit ACDEU170C2ZGIMR410 and 2 outdoor units ACDCUA08513, on a 3-phase, 415 V outdoor supply and a single-phase, 230 V indoor supply, with a 100 A breaker, and a pipe run of 5 m between outdoor and indoor unit. The order states a total capacity of 102 TR. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote 6 sets of Voltas air-cooled ductable split model ACADS17023 under the R410A series, each with indoor unit ACDEU170C2ZGIMR410 and 2 outdoor units ACDCUA08513, on a 3-phase, 415 V outdoor supply and a single-phase, 230 V indoor supply, with a 100 A breaker and a 3C x 1.5 sq mm interlocking cable between indoor and outdoor unit, and a pipe run of 5 m between outdoor and indoor unit. The order states a total capacity of 102 TR. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote 4 sets of Voltas air-cooled ductable split model ACADS11023 under the R410A series, each with indoor unit ACDEU110C2ZGIMR410 and 1 outdoor unit ACDCUA05513, on a 3-phase, 415 V outdoor supply and a single-phase, 230 V indoor supply, with a 50 A breaker and a 3C x 1.5 sq mm interlocking cable between indoor and outdoor unit, and a pipe run of 5 m between outdoor and indoor unit. The order states a total capacity of 42 TR. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote 4 sets of Voltas air-cooled ductable split model ACADS11023 under the R410A series, each with indoor unit ACDEU110C2ZGIMR410 and 2 outdoor units ACDCUA05513, on a 3-phase, 415 V outdoor supply and a single-phase, 230 V indoor supply, with a 63 A breaker and a 3C x 1.5 sq mm interlocking cable between indoor and outdoor unit, and a pipe run of 5 m between outdoor and indoor unit. The order states a total capacity of 44 TR. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote 3 sets of Voltas air-cooled ductable split model ACADS20022 under the R407C series, each with indoor unit ACDEU150C2ZGIM and 2 outdoor units ACDCUA10011, on a 3-phase, 415 V outdoor supply and a single-phase, 230 V indoor supply, with a 125 A breaker and a 3C x 1.5 sq mm interlocking cable between indoor and outdoor unit, and a pipe run of 12 m between outdoor and indoor unit. The order states a total capacity of 60 TR. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote 3 sets of Voltas air-cooled ductable split model ACADS20022 under the R407C series, each with indoor unit ACDEU200C2ZGIM and 2 outdoor units ACDCUA10011, on a 3-phase, 415 V outdoor supply and a single-phase, 230 V indoor supply, with a 125 A breaker and a 3C x 1.5 sq mm interlocking cable between indoor and outdoor unit, and a pipe run of 12 m between outdoor and indoor unit. The order states a total capacity of 60 TR. It is ready to send.
Verdict: Needs approval.
The agent's request. Please quote 3 sets of Voltas air-cooled ductable split model ACADS20022 under the R407C series, each with indoor unit ACDEU200C2ZGIM and 2 outdoor units ACDCUA10011, on a 3-phase, 415 V outdoor supply and a single-phase, 230 V indoor supply, with a 125 A breaker and a 3C x 1.5 sq mm interlocking cable between indoor and outdoor unit, and a pipe run of 5 m between outdoor and indoor unit. The order states a total capacity of 60 TR. It is ready to send.
Verdict: Allowed.
The text of the narrated walkthrough, step by step.