Predictika · Industrial and commercial heating
An AI sales agent prepares a compact gas burner line item for a boiler or process heater: the burner size, the gas, the control type, the gas train, the output it must deliver and the gas pressure the site supplies. Before it goes out, the agent sends it to Predictika, which checks it against a declarative model of the manufacturer's published burner tables and returns a verdict, every reason and the figures it looked up.
This validator models burner line items for the Weishaupt WG10, WG20, WG30 and WG40 compact gas burners as listed in the manufacturer's brochure Digitale Gasbrenner WG5 bis WG40 (print number 83214101, June 2019), not just the scenarios shown below.
Any burner line item for these four burners that touches these rules is in scope — not only the scenarios pictured here. Not covered: prices (Weishaupt does not publish list prices, so this validator produces no price build-up), the WG5, the larger Weishaupt burner series, oil and dual-fuel burners, the newer WG40 variants beyond the 2019 brochure, boiler and furnace sizing, the output-versus-furnace-pressure working diagrams, burner motor and fan data, and approvals and certificates. Assumptions: the brochure lists minimum gas pressure at output steps, so the validator uses the next listed step at or above the design output; the altitude derating of about 1 percent per 100 m is treated as a limit; and the pressure regulator requirement above 150 mbar for the W-MF 512 gas trains is taken from the brochure's accessory lists.
8 scenarios in 4 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| Minimum gas pressure that depends on burner, gas, gas train and output step | Only with workarounds The pressure is a lookup over burner size, three gases, up to six gas trains and the output step, 40 columns in all, and a rule has to compare it with the supply pressure and with the figure the rep typed in. | The pressure for the selected burner, gas, gas train and output step is looked up on every call and compared with the supply and the stated figure. |
| A load swing that the control type cannot follow | Only with care Each burner and gas has its own output range and control range for single-stage, two-stage and modulating, so the rep has to know which combination is allowed before the order reaches review. | The range and control range are looked up for the selected combination and compared with the highest and lowest load on every call. |
| Options that exist only on some burners and only with one firing manager | Only with care Whether continuous operation, a fieldbus module, speed control or oxygen trim is available depends on the burner size and on which firing manager that control type includes, and each combination is its own rule. | Each option is checked against the burner and control type, and every option that cannot be fitted is reported together. |
| Pressure regulator, altitude and ambient limits | Only with care The regulator requirement depends on the gas train and the supply pressure, the derating on the installation altitude, and the ambient limit on the site, all separate from the burner choice. | All three are checked on every call from the supply pressure, the altitude and the ambient temperature on the quote. |
| Every problem returned in one answer | Only with workarounds Rules tend to fire as the quote is saved or a step is completed, so a rep often fixes one error and meets the next. | All findings come back together, whatever order the choices arrived in. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | The standard 1/2 inch gas train is for supply pressure up to 50 mbar, but the supply here is 60 mbar. |
| 2 | At a supply pressure of 120 mbar this gas train needs an upstream FRS pressure regulator, and the quote does not have one. |
| 3 | The plant needs to run from 100 kW down to 50 kW, but this burner has a control range of only 1:1. |
| 4 | The plant needs to run from 100 kW down to 40 kW, but this burner has a control range of only 1:2. |
| 5 | The selected gas train is not listed for this burner and gas in the supply-pressure table. |
| 6 | The design output of 30 kW is below the 40 kW minimum of this burner. |
| 7 | The design output of 120 kW is above the 110 kW maximum of this burner. |
| 8 | The plant needs to run as low as 30 kW, but this burner cannot go below 35 kW. |
| 9 | The plant needs to run from 200 kW down to 35 kW, but this burner has a control range of only 1:5.7. |
| 10 | This burner is not offered in the selected control type for this gas. |
| 11 | The plant needs to run as low as 55 kW, but this burner cannot go below 60 kW. |
| 12 | The plant needs to run from 300 kW down to 55 kW, but this burner has a control range of only 1:4. |
| 13 | This burner needs 20 mbar before the ball valve at this output, but the gas supply gives only 18 mbar. |
| 14 | This burner needs 21 mbar before the ball valve at this output, but the gas supply gives only 20 mbar. |
| 15 | This burner needs 61 mbar before the ball valve at this output, but the gas supply gives only 60 mbar. |
| 16 | At a supply pressure of 160 mbar this gas train needs an upstream FRS pressure regulator, and the quote does not have one. |
| 17 | At this installation altitude the burner is derated by about 1 percent per 100 m to 315 kW, below the design output of 340 kW. |
| 18 | A supply pressure of 330 mbar is above the standard 300 mbar design; Weishaupt can release up to 360 mbar after a check with the factory. |
| 19 | A supply pressure of 400 mbar is above the 360 mbar that Weishaupt can release. |
| 20 | The supply pressure of 12 mbar is under the 15 mbar minimum flow pressure the brochure recommends; a person should confirm it. |
| 21 | This burner needs 13 mbar before the ball valve at this output, but the gas supply gives only 12 mbar. |
| 22 | The supply pressure of 14 mbar is under the 15 mbar minimum flow pressure the brochure recommends; a person should confirm it. |
| 23 | An ambient temperature of -20 degrees C is outside the -15 to +40 degrees C range for gas operation; use outside it needs written consent from Max Weishaupt GmbH. |
| 24 | The quote states 13 mbar required before the ball valve, but the table gives 14 mbar. |
| 25 | The quote states a control range of 1:7, but this burner has 1:5.7. |
| 26 | Operation for more than 24 hours without shutdown needs the W-FM25 firing manager in its continuous-operation version, and this burner does not have the W-FM25. |
| 27 | Speed control of the fan is offered only for the WG30 and WG40. |
| 28 | Oxygen trim is offered only for the modulating WG20 and for the WG30 and WG40. |
| 29 | The fieldbus and analog modules plug into the W-FM25 firing manager, and this burner does not have the W-FM25. |
| 30 | Flame head extensions are offered in 100, 200 and 300 mm; the quote has 150 mm. |
| 31 | The lowest load of 160 kW is above the design output of 150 kW. |
| 32 | The design output of 55 kW is above the 50 kW maximum of this burner. |
| 33 | The design output of 380 kW is above the 350 kW maximum of this burner. |
| 34 | The plant needs to run as low as 30 kW, but this burner cannot go below 40 kW. |
| 35 | The plant needs to run from 380 kW down to 30 kW, but this burner has a control range of only 1:5. |
| 36 | At a supply pressure of 200 mbar this gas train needs an upstream FRS pressure regulator, and the quote does not have one. |
| 37 | The quote states 19 mbar required before the ball valve, but the table gives 33 mbar. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Please quote a Weishaupt WG20 gas burner, two-stage, on natural gas LL with the W-MF 512, 1 inch gas train. The plant needs 200 kW at full load and runs down to 100 kW. The gas supply gives 30 mbar at the ball valve. The quote includes continuous operation, oxygen trim and a fieldbus module. The quote states a control range of 1:2 and 20 mbar required before the ball valve. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a Weishaupt WG20 gas burner, modulating, on natural gas LL with the W-MF 512, 1 inch gas train. The plant needs 200 kW at full load and runs down to 100 kW. The gas supply gives 30 mbar at the ball valve. The quote includes continuous operation, oxygen trim and a fieldbus module. The quote states a control range of 1:5.7 and 20 mbar required before the ball valve. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a Weishaupt WG40 gas burner, modulating, on natural gas E with the W-MF 512, 1 1/2 inch gas train. The plant needs 520 kW at full load and runs down to 100 kW. The gas supply gives 20 mbar at the ball valve and the furnace pressure is 4 mbar. The quote states a control range of 1:7 and 21 mbar required before the ball valve. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a Weishaupt WG40 gas burner, modulating, on natural gas E with the DMV 5065/12, DN65 gas train. The plant needs 520 kW at full load and runs down to 100 kW. The gas supply gives 20 mbar at the ball valve and the furnace pressure is 4 mbar. The quote states a control range of 1:7 and 20 mbar required before the ball valve. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a Weishaupt WG20 gas burner, single-stage, on natural gas E with the W-MF 512, 1 inch gas train. The plant needs 180 kW at full load and runs down to 60 kW. The gas supply gives 25 mbar at the ball valve. The quote states a control range of 1:5.7 and 15 mbar required before the ball valve. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a Weishaupt WG20 gas burner, modulating, on natural gas E with the W-MF 512, 1 inch gas train. The plant needs 180 kW at full load and runs down to 60 kW. The gas supply gives 25 mbar at the ball valve. The quote states a control range of 1:5.7 and 15 mbar required before the ball valve. It is ready to send.
Verdict: Allowed.
The agent's request. Please quote a Weishaupt WG30 gas burner, modulating, on natural gas E with the W-MF 512, 1 1/2 inch gas train. The plant needs 340 kW at full load and runs down to 80 kW. The gas supply gives 330 mbar at the ball valve. The site is at 1,000 m altitude. The quote includes an FRS pressure regulator. The quote states a control range of 1:5 and 16 mbar required before the ball valve. It is ready to send.
Verdict: Blocked.
The agent's request. Please quote a Weishaupt WG40 gas burner, modulating, on natural gas E with the W-MF 512, 1 1/2 inch gas train. The plant needs 340 kW at full load and runs down to 80 kW. The gas supply gives 330 mbar at the ball valve. The site is at 1,000 m altitude. The quote includes an FRS pressure regulator. The quote states a control range of 1:7 and 13 mbar required before the ball valve. It is ready to send.
Verdict: Needs approval.
The text of the narrated walkthrough, step by step.