An AI sales agent prepares an order for high-efficiency circulator pumps with a model, a supply voltage, a pipe size and the conditions the pumps will run in. Before it goes out, the agent sends it to Predictika, which checks it against a declarative model of the data sheet limits and returns a verdict, every reason and the figures it computed.
This validator models orders for the Wilo-Stratos MAXO US 60 Hz circulators listed in the Wilo submittal data sheet, not just the scenarios shown below.
Any order for these Stratos MAXO models that touches these rules is in scope — not only the scenarios pictured here. Not covered: prices (the data sheet has none, so this validator produces no price build-up or line-item quote), duty-point selection (flow and head curves), the CIF communication modules and accessories, other Wilo pump families and the 50 Hz or flanged-variant data sheets. Assumption: the data sheet gives the minimum suction head at 122, 203 and 230 degrees F; the validator uses the 122 degree value up to 122 degrees F, the 203 degree value above that up to 203 degrees F and the 230 degree value above 203 degrees F (the next listed temperature up).
6 scenarios in 3 groups · each group runs from the agent’s first attempt to the outcome · click one to switch
Illustrative agent statement. The validator receives the structured request below.
Proposing agent: AI sales agent (scripted)
Before sending, the agent must call Recorded run
What this means
Our assessment of what a typical rules-based CPQ (product rules, price rules and validation rules, as in Salesforce CPQ) does with the same cases. It is a judgment about effort and reliability, not a claim that nothing can be built.
| What the validator caught | Typical rules-based CPQ | Predictika |
|---|---|---|
| Models that run on 115 V and models that do not | Only with care Voltage is an option on one line and the model is another, so each of the nine 230 V-only models needs its own availability rule, and a new model is a new rule. | The model and the supply voltage travel in one request and every pairing is checked together. |
| Minimum suction head that depends on model and fluid temperature | Only with workarounds The required head is a lookup by model group and temperature band, compared with a number the rep types in; that means a table plus a validation rule per model group, and a boundary such as 203 versus 204 degrees F is easy to get wrong. | The required head is computed from the model and temperature on every call and compared with the inlet pressure, with the boundaries tested. |
| Pipe size that must match the pump flanges | Only with care A product rule per model and pipe size; it works, but each new model adds more rules to maintain. | The model and pipe size are in one request and checked together on every call. |
| Every problem returned in one answer | Only with workarounds Rules tend to fire as the order is saved or a step is completed, so a rep often fixes one error and meets the next. | All findings come back together, whatever order the choices arrived in. |
Every rule is checked on every call, in any order the choices arrive; one problem never hides another. Blocking findings stop the quote; approval findings need a person to sign off; everything else is computed.
| 1 | Stratos MAXO 1.25x3-30 is offered only for 1~230-240 V supply; the order specifies a 115 V supply. |
| 2 | Stratos MAXO 3x3-40 is offered only for 1~230-240 V supply; the order specifies a 115 V supply. |
| 3 | The pipe size on the order, 2 in., does not match the pipe connections of Stratos MAXO 1.25x3-15. |
| 4 | The pipe size on the order, 3 in., does not match the pipe connections of Stratos MAXO 2x3-35. |
| 5 | The inlet pressure of 4.3 PSI is below the 14.2 PSI minimum suction head this pump needs at a fluid temperature of 123 degrees F. |
| 6 | The inlet pressure of 14.2 PSI is below the 22.8 PSI minimum suction head this pump needs at a fluid temperature of 204 degrees F. |
| 7 | A fluid temperature of 231 degrees F is outside the 14 to 230 degrees F range of the Stratos MAXO. |
| 8 | A fluid temperature of 13 degrees F is outside the 14 to 230 degrees F range of the Stratos MAXO. |
| 9 | An ambient temperature of 105 degrees F is outside the 14 to 104 degrees F range of the Stratos MAXO. |
| 10 | An ambient temperature of 13 degrees F is outside the 14 to 104 degrees F range of the Stratos MAXO. |
| 11 | A system pressure of 146 PSI is above the 145 PSI maximum operating pressure of the Stratos MAXO. |
| 12 | The inlet pressure of 17 PSI is below the 17.1 PSI minimum suction head this pump needs at a fluid temperature of 180 degrees F. |
| 13 | The inlet pressure of 30 PSI is below the 32.7 PSI minimum suction head this pump needs at a fluid temperature of 220 degrees F. |
| 14 | The inlet pressure of 5 PSI is below the 32.7 PSI minimum suction head this pump needs at a fluid temperature of 235 degrees F. |
| 15 | The pipe size on the order, 2 in., does not match the pipe connections of Stratos MAXO 3x3-40. |
| 16 | A fluid temperature of 235 degrees F is outside the 14 to 230 degrees F range of the Stratos MAXO. |
| 17 | An ambient temperature of 110 degrees F is outside the 14 to 104 degrees F range of the Stratos MAXO. |
| 18 | A system pressure of 150 PSI is above the 145 PSI maximum operating pressure of the Stratos MAXO. |
The recorded result of the validator for each scenario on this page: the request the AI agent sent, the verdict, and every finding, in the order they appear above.
The agent's request. Please order 4 Stratos MAXO 3x3-40 circulators on a 115 V supply for 3 in. piping. The fluid runs at 180 degrees F, the ambient temperature is 85 degrees F, the system pressure is 90 PSI and the inlet pressure at the pumps is 15 PSI. It is ready to send.
Verdict: Blocked.
The agent's request. Please order 4 Stratos MAXO 3x3-40 circulators on a 230 V supply for 3 in. piping. The fluid runs at 180 degrees F, the ambient temperature is 85 degrees F, the system pressure is 90 PSI and the inlet pressure at the pumps is 25 PSI. It is ready to send.
Verdict: Allowed.
The agent's request. Please order 3 Stratos MAXO 2x3-35 circulators on a 230 V supply for 3 in. piping. The fluid runs at 215 degrees F, the ambient temperature is 80 degrees F, the system pressure is 100 PSI and the inlet pressure at the pumps is 20 PSI. It is ready to send.
Verdict: Blocked.
The agent's request. Please order 3 Stratos MAXO 3x3-40 circulators on a 230 V supply for 3 in. piping. The fluid runs at 215 degrees F, the ambient temperature is 80 degrees F, the system pressure is 100 PSI and the inlet pressure at the pumps is 20 PSI. It is ready to send.
Verdict: Blocked.
The agent's request. Please order 3 Stratos MAXO 3x3-40 circulators on a 230 V supply for 3 in. piping. The fluid runs at 215 degrees F, the ambient temperature is 80 degrees F, the system pressure is 100 PSI and the inlet pressure at the pumps is 35 PSI. It is ready to send.
Verdict: Allowed.
The agent's request. Please order 5 Stratos MAXO 1.25x3-52 circulators on a 230 V supply for 1 1/4 in. piping. The fluid runs at 240 degrees F, the ambient temperature is 110 degrees F, the system pressure is 160 PSI and the inlet pressure at the pumps is 30 PSI. It is ready to send.
Verdict: Blocked.
The text of the narrated walkthrough, step by step.